Deptford Power Station

Coordinates:51°28′57″N0°01′13″W / 51.4824°N 0.0203°W /51.4824; -0.0203
From Wikipedia, the free encyclopedia
This article includes a list ofgeneral references, butit lacks sufficient correspondinginline citations. Please help toimprove this article byintroducing more precise citations.(April 2017) (Learn how and when to remove this message)

Deptford Power Station
Deptford West Power Station
Viewed from the east in July 1973
Map
CountryEngland
LocationGreater London
Coordinates51°28′57″N0°01′13″W / 51.4824°N 0.0203°W /51.4824; -0.0203
StatusDecommissioned and demolished
Construction began1888 (Deptford East LP)
1926 (Deptford West)
1947 (Deptford East HP)
Commission date1891 (Deptford East LP)
1929 (Deptford West)
1953 (Deptford East HP)
Decommission dateLate 1960s (Deptford East LP)
1972 (Deptford West)
1983 (Deptford East HP)
OwnerAs operator
OperatorsLondon Electric Supply Corporation
(1891–1925)
London Power Company
(1925–1948)
British Electricity Authority
(1948–1955)
Central Electricity Authority
(1955–1957)
Central Electricity Generating Board
(1958–1983)
Thermal power station
Primary fuelCoal
ChimneysFerranti station: 2 (150 feet); Deptford East: 1 polygonal; Deptford West: 2 tall fluted stacks
Cooling towersNone
Cooling sourceRiver water
Power generation
Units operational(See text)
Units decommissionedAll
Nameplate capacity448 MW (70 MW approx Deptford East LP, 212 MW Deptford West, 166 MW Deptford East HP)
Annual net output(See graphs below)
External links
CommonsRelated media on Commons

grid referenceTQ374778
A London Electricity Supply Corporation sub-station in Greenwich High Road 2009

Three distinctcoal-fired power stations were built atDeptford on the south bank of theRiver Thames, the first of which is regarded as the first central high-voltage power station in the world.

History

[edit]

Deptford East (Low Pressure)

[edit]

One of the first premises in London to be supplied with electricity was theGrosvenor Gallery inBond Street. It was the brainchild of theEarl of Crawford, who had been inspired in 1881 by theInternational Exposition of Electricity in Paris. A power plant was duly built at the Grosvenor Gallery. It was designed to supply just lighting for the gallery but it was soon extended to supply nearby shops and residences and a larger power plant was opened in 1884. With the prospect of expanding still further, theLondon Electric Supply Corporation was formed (LESCo). Principal shareholders were the Earl of Crawford, his friend SirCoutts Lindsay and Sir Coutts’ brother,Lord Wantage.

There were environmental objections to large-scale power generation in Central London, so LESCo decided to move to a new site in Deptford and to use the Grosvenor Gallery site as a substation. A feature of the Grosvenor scheme was its use ofalternating current (AC) in preference todirect current (DC). The use of AC allowed the voltage to be raised to 10 kV for transmission between Deptford and Grosvenor Gallery. High-voltage cables were laid alongside theLondon & Greenwich Railway line, but cable design at that time was rudimentary, having short lengths and many joints. This caused a voltage drop of some 10% from end to end. In order to supply at 10 kV at Grosvenor Gallery substation, the design voltage at Deptford had to be set at 11 kV, which is why national transmission voltages became standardised in multiples of eleven.[1]

Sebastian de Ferranti was appointed to engineer the scheme, and the world's first central power station opened at Deptford in 1889. ‘Central’ means that it was remote from most of its consumers. To distinguish it from later adjacent developments, Ferranti's power station subsequently took the name Deptford East LP. It was pioneering not just because it was "central" but because of its unprecedented scale and high voltage. It was built on a 3-acre warehouse site called The Stowage which once belonged to theEast India Company and was later used by theGeneral Steam Navigation Company.

The first generating machinery to be installed at Deptford was that which had served at the Grosvenor Gallery station. The alternators were of the Ferranti type, the first being driven by belts from three Marshall engines of 250 H.P., 250 H.P., and 400 H.P. respectively. The engines could be connected by clutches as the load required, all three engines being clutched in to drive the alternator at full load. The other generator was driven by ropes from a 750 H.P. Corliss engine, built by Hick, Hargreaves and Co. The generators were at that time the largest in the country. They had armatures 8ft. 6in. diameter, running at 250 revolutions per minute and produced single-phase current at 2500 volts, this pressure being increased to 10,000 volts for transmission by step-up transformers.[2]

In 1889 two 10,000 Volt Ferranti alternators driven by two 1500 hpHick, Hargreaves reciprocating steam engines were installed,[3] supplied by 24 boilers[4] burning coal brought by collier from Newcastle. There were teething problems both at the power station and at the Grosvenor Gallery substation, resulting in lengthy shutdowns and loss of customers. Ferranti himself was sacked in 1891 and succeeded by G. W. Partridge as chief engineer. The plant was rebuilt withsteam turbines and other improvements, and electricity supply eventually became reliable. Demand increased steadily and by 1912 plant of 16,000kW capacity was installed supplying customers through three different systems as follows:

  • Domestic and commercial customers at 83.33-cycle single-phase AC.
  • Industrial and other customers with three-wire DC and a choice of two voltages.
  • Trams, railways and other customers at 25-cycle single-phase AC.

In 1923 the AC plant comprised: 1 × 700 kW, 2 × 1,000 kW, 1 × 1,200 kW, 1 × 1,400 and 5 × 2,000 kW reciprocating engine driven generators; there were 2 × 3,500 kW, 2 × 7,500 and 1 × 15,000 kW turbo-alternators.[5] The DC supply was generated by a single 200 kW reciprocating engine and generator. The total installed capacity was 52.5 MW. The boiler plant produced a total of 490,000 lb/hr (61.73 kg/s) of steam. In 1923 the station generated 53.007 GWh of electricity, some of this was used in the plant,  the total amount sold was 46.044 GWh. The revenue from sales of current was £362,133, this gave a surplus of revenue over expenses of £143,574.[5]

By 1929 installed capacity had reached 100MW and the plant comprised three turbo-alternators of 4,000 KW and one of 7,500 kW capacity, generating at 2500 volts to supply 83 cycle/second load; two machines of 8,750 kW and 15,000 kW respectively to supply industrial load at 6,600 Volts 3 phase, 25 cycles/sec; and for the Southern Railway service there are three 20,000 kW sets, generating three-phase 25 cycles/sec at 11,000 volts.[2]

When Britain eventually standardised to 50-cycle three-phase AC, Deptford East LP was downsized to just a few 25-cycle turbine-generators. To feed the 50-cycle National Grid from the LP station, a frequency converter was installed in Deptford West. This motor-generator was commonly known asThe Freak. Deptford East LP closed in the late 1960s.

Deptford West

[edit]

In 1925, ten electricity supply companies, LESCo among them, amalgamated to become theLondon Power Company (LPC). Deptford West was conceived by LESCo but was built by LPC and was engineered by Leonard Pearce. The turbine house basement was built in a former dry dock. Initially in 1929 the station had four turbine alternators, two rated at 27,500 kW and two at 35,000 kW each, a bank of coal-fired boilers (Eight Babcock and Wilcox 90,000 Ib/hr and four of Stirling 130,000 lb/hr ) and a single large concrete chimney at the northern end.[2][6] Four additional turbine-generations were added in the late 1930s together with three house sets, additional boilers and a second chimney. Staff claimed that the basement of No. 2 turbine-generator was haunted by the ghosts of those who had died on the gibbets alongside the dry dock. This may have been on the site one of the original dry docks founded by Henry VIII for the Royal Navy. Deptford West closed in 1972.

The electricity output from Deptford West power station was as follows.[7][8][9][10]

Deptford West annual electricity output GWh.

Graphs are unavailable due to technical issues. Updates on reimplementing the Graph extension, which will be known as the Chart extension, can be found onPhabricator and onMediaWiki.org.

Deptford East (High Pressure)

[edit]

When the electricity industry was nationalised in 1948, power generation came under the auspices of theBritish Electricity Authority. Deptford East HP opened in 1953 with three 52.5 MW turbine-generators, a range of coal-fired boilers (2 × 225,000 lb/hr (28.3 kg/s) and 5 × 250,000 lb/hr (31.5 kg/s); delivering at 950 psi and 925 °F (496 °C))[11] and a single chimney. The original plan had been to demolish the LP station to make way for an extension of the HP station, doubling its size. This was never realised because the rapid rate of rise of electricity demand needed much larger power plants than could be accommodated at Deptford. The HP station closed in 1983 under the auspices of theCEGB.

The electricity output from Deptford East power station was as follows.[8][9][10]

Deptford East annual electricity output GWh.

Graphs are unavailable due to technical issues. Updates on reimplementing the Graph extension, which will be known as the Chart extension, can be found onPhabricator and onMediaWiki.org.

Deptford site as a whole

[edit]

The Deptford site was targeted in both World Wars. In 1916, aZeppelin dropped a 250 lb bomb, killing one man and putting the entire traction and industrial switchboard out of action, but lighting supplies were restored within 12 minutes, and traction supplies were restored within 24 hours. DuringWorld War II, 27 Deptford staff were killed by bombs. The most extensive damage was caused by a bomb on the West switch house. The site as a whole was redeveloped during the 1990s with luxury apartments and a slipway for dinghies. The coaling jetty in the Thames survives. Also surviving are some walls of the west boiler house, which have been incorporated into the apartment structure. A nearby park was developed from a derelict site and was named Ferranti Park as a tribute to one of the great industrial pioneers.

A summary of all the turbine-generator ratings in the mid-1960s:[8]

SiteGenerators
Deptford East LP70 MW approx from 3 × 20 MW British Thomson-Houston-Brown Boveri, 1 × 25 MW British Thomson-Houston, 1 × 25 MW Richardson-Westgarth-BT-H turbo-alternators
Deptford West212 MW (2 x 30 MW British Thomson-Houston + 3 x 35 MW Metropolitan Vickers + 1 x 50 MW Metropoliyan Vickers + 7 MW from three house sets)
Deptford East HP166 MW (3 x 55.5 MW Metro-Vickers turbo-alternators)
Deptford Site Total448 MW

This compares with 4,000 MW atDrax and 3,200 MW atHinkley Point C. Although Deptford was small by modern standards, its contribution to the war effort and to the post-war recovery period was invaluable.

A summary of the boiler capacities and steam conditions.[7][8]

Boiler capacity and steam conditions
SiteBoilers (No. and manufacturer)Boiler capacity (steam flow)Steam condition (at turbine stop valves)
Deptford East LP10 Stirling2,245,000 lb/hr (282.9 kg/s)300 psi (20.7 bar), 357 °C
Deptford East HP2 Babcock and Wilcox

5 Foster Wheeler

900 psi (62.1 bar), 482 °C
Deptford West4 Babcock and Wilcox

4 Stirling

2 Babcock and Wilcox

2 Thompson

1 Thompson La Mont Steam Generator

2,486,000 lb/hr (313.2 kg/s)350 psi (24.1 bar), 399 °C

Coal supply

[edit]

Coal was brought by sea fromNorth East England orSouth Wales. The LPC and its nationalised successors had its own fleet ofcoastalcolliers for this service, such as the 2,268GRT SSFrancis Fladgate built in 1933 and 2,904 GRT SSOliver Bury built in 1945.[12]

References

[edit]
  1. ^Cochrane, Rob."FERRANTI'S DEPTFORD POWER STATION"(PDF).
  2. ^abcThe Engineer 1929-03-29: Vol 147 Iss 3820. Internet Archive. 29 March 1929.{{cite book}}: CS1 maint: others (link)
  3. ^Wilson, J. F. (1988)."The Deptford experience".Ferranti and the British Electrical Industry, 1864-1930 (illustrated, reprint ed.). Manchester University Press. p. 35.ISBN 978-0719023699. Retrieved28 September 2016.
  4. ^"Ferranti's Deptford Power Station".CEGB. HISTELEC NEWS. Archived fromthe original on 11 June 2008. Retrieved10 August 2008.
  5. ^abElectricity Commissioners (1925).Electricity Supply - 1920-1923. London: HMSO. pp. 176–79,448–53.
  6. ^Royal Commission on the Historical Monuments of England (1995).The Power Stations of the Lower Thames. Swindon: National Monuments Record Centre.
  7. ^abCEGB Statistical Yearbooks (various years). CEGB, London.
  8. ^abcdGarrett, Frederick C., ed. (1959).Garcke's Manual of Electricity Supply vol.56. London: Electrical Press. pp. A-49–50, A-119.
  9. ^abCEGBAnnual Report and Accounts, various years
  10. ^abElectricity Commission,Generation of Electricity in Great Britain year ended 31st December 1946. London: HMSO, 1947.
  11. ^Pugh, H.V. (November 1957). "The Generation of Electricity in the London Area".Proceedings of the Institution of Electrical Engineers.105 (23):487–48.
  12. ^Anderson, James B (2008). Sommerville, Iain (ed.)."Ships built by the Burntisland Shipbuilding Company Ltd: arranged by date of launch".Welcome to Burntisland. Iain Sommerville. Retrieved15 June 2011.

Bibliography

[edit]
  • Cochrane, Rob,Cradle of Power, the Story of Deptford Power Stations.

External links

[edit]
Wikimedia Commons has media related toDeptford Power Station.
Companies and
organisations
Current
Former
Power stations
Biomass
Active
Coal
Closed
Gas
Active
Closed
Future
Incinerators/
waste
Active
Closed
Oil
Active
Closed
Wind
Active
Preceded by Largest Power Station in the UK
1891–1901
Succeeded by
Retrieved from "https://en.wikipedia.org/w/index.php?title=Deptford_Power_Station&oldid=1275854657"