CROSS-REFERENCE TO RELATED APPLICATIONThis application is a Continuation-in-Part of Application Serial No. US 2005/0252226 A1, entitled “Heating/Cooling System” and filed May 11, 2005, the contents of which are incorporated herein by reference.
FIELD OF THE INVENTIONThe present invention relates generally to heating and cooling systems and more specifically to a heating and cooling system with multiple compressors, multiple heat outputs and the control system for managing the system.
BACKGROUND OF THE INVENTIONHeat pump systems have found widespread application for heating and cooling homes and businesses. Because heat pump systems utilize the same primary components for both heating and cooling, they eliminate the need for separate heating and cooling systems and are therefore economical to install and use. Heat pump systems are also highly efficient, resulting in decreased energy costs to the consumer. As a result, the demand for heat pump systems in residential and business applications has continued to grow in recent years.
The use of conventional heat pump systems in colder climates, however, presents significant challenges. In heating mode, a heat pump system draws heat energy from the outdoor air to heat an indoor space. Even at low ambient temperatures, heat may be drawn from the outdoor environment by evaporating refrigerant in an outdoor evaporator. The evaporated refrigerant is then compressed by one or more compressors and then cycled to an indoor condenser where the energy of the compressed refrigerant is released to the indoor space. The refrigerant is then cycled back to the outdoor evaporator to repeat the cycle.
At very low temperatures, however, it becomes increasingly difficult to draw heat from the outdoor environment. In addition, at very low temperatures, the outdoor heat exchange coil is very susceptible to frost build up, which limits air flow across the coil. As a result, the performance and efficiency of heat pump systems decreases drastically at very low ambient temperatures when heating capacity is most needed. To address this issue, increased compressor capacity is required for heat pump systems installed in colder climates. Single compressor systems have been utilized that can provide heating at low to moderate ambient temperatures, but such systems typically demonstrate decreased efficiency and performance at higher temperatures. Such systems must cycle on and off frequently at higher ambient temperatures, resulting in a reduced lifespan for the compressor and decreased system efficiency. Variable speed compressors have been used to address this problem, but these types of compressors are expensive and lead to increased installation costs for the system.
Multiple compressor systems have been proposed to adapt the heat pump concept for use in colder climates. These systems utilize a primary compressor for heating and cooling in moderate temperatures, and also include a booster compressor to provide increased capacity at very low temperatures. An economizer, which utilizes a diverted portion of the refrigerant flow to subcool the refrigerant flowing to the evaporator, may also be used to provide increased heating capacity at very cold temperatures. Systems utilizing multiple compressors and an economizer are disclosed, for example, in U.S. Pat. Nos. 5,927,088, 6,276,148 and 6,931,871 issued to Shaw. Although the systems disclosed in these patents address the need to provide increased heating capacity at very cold temperatures, those of skill in the art have continued to seek sophisticated methods that effectively control the multiple compressors to maximize system efficiency and utilize the full output potential of the compressors.
In particular, prior art systems have controlled multiple compressors based on limited system inputs. For example, the '148 and '871 patents issued to Shaw disclose dual compressor systems that select compressor output in response to decreases and/or increases in outdoor ambient temperature. The '871 patent issued to Shaw discloses a system that selects compressor output in response to a multi-step indoor thermostat and the system low side pressure, which pressure is commensurate with outdoor ambient air temperature during all heating cycle modes of operation. These control methodologies, however, may lead to frequent calls for changes in compressor output, which will cause one or both of the compressors to cycle on and off. Although important to prevent unsafe and inefficient compressor operation, a system control that more effectively manages when compressors are turned on and off is desirable. Such a system may lead to increased compressor run times in a consistent output condition, which increases the life of the compressors and overall system efficiency.
Prior art systems have disclosed the use of multiple compressors to provide heat for an indoor forced air heat exchanger. With multiple compressors, however, additional heating capacity is present that may also be utilized for an additional indoor heating system such as a hydronic floor system. The heat pump system may also provide energy for a tap water heater. With these additional heating components integrated into the heat pump system, the potential output of the compressors may be more fully realized, providing further justification for the cost of the system. Further, if properly configured and controlled, these additional heating components may be used to absorb excess energy produced by the compressors to address and limit high pressure and temperature conditions. Also, with multiple heating components receiving energy input from the compressors, compressor run time can be increased. With the compressors cycling on and off less frequently, the life span and efficiency of the compressors is increased.
Despite the increased capacity provided by multiple compressors, heat pump systems installed in very cold climates may require some form of back up heating to address the very coldest conditions. Prior art systems, however, have not effectively integrated control of the back up heating system with the control of the heat pump system. As a result, the back up heating system, which performs at lower efficiency, is over utilized as compared to the heat pump system, leading to increased energy costs. If the two systems are effectively integrated and controlled, the higher efficiency of the heat pump system may be more fully utilized even during the coldest months of the year.
Finally, those of skill in the art have sought a heat pump system that effectively integrates utility Load Management Control. Load Management Control, or LMC, allows a utility company to remotely and temporarily shut down certain users' heating and cooling systems at times when the utility is experiencing peak loads. Because this capability is desirable for utility companies, energy consumers that implement this feature may receive decreased energy rates, tax incentives or other consideration. To implement LMC, an auxiliary heating system with a different energy source, such as a gas furnace, is typically required to provide heat when the utility initiates a system shut down in cold weather conditions. Control of this alternative heating source is preferably integrated with control of the heat pump system so that the system effectively and efficiently transitions to the alternative heat source when a shut down command is received, and also easily transitions back to the main heating system when the shut down condition terminates.
Accordingly, an object of the present invention is to provide a heat pump system for use in colder climates that is economical to install and use.
An additional object of the present invention is to provide a heat pump system with multiple compressors that effectively controls the compressors to maximize system efficiency and utilize the full output potential of the compressors.
A further object of the present invention is to provide a heat pump system with multiple heat outputs including a forced air heater, a hydronic floor heating system and/or a water heater.
Yet another object of the present invention is to provide a heat pump control system that may easily and effectively divert compressor energy to multiple heat outputs to fully utilize the output of the compressors, address high pressure and temperature conditions, increase compressor run times, decrease compressor cycling and maximize the overall efficiency of the system.
Still another object of the present invention is to provide a heat pump control system that effectively integrates a back up heating system for use in the very coldest conditions.
A still further object of the present invention is to provide a heat pump system that effectively integrates utility Load Management Control.
Additionally, an object of the present invention is to provide a heat pump system that may effectively defrost the outdoor coil.
Finally, an object of the present invention is to provide a heat pump system that provides energy for heating tap water when the system is in use for either heating or cooling, and also minimizes the use of the water heater element under all conditions.
SUMMARY OF THE INVENTIONThe preferred embodiment of the present invention provides increased heating capacity through the use of a primary compressor, a booster compressor and an economizer. The system effectively utilizes this heating capacity with three heat exchangers that provide 1) indoor air heating or cooling, 2) hydronic floor heating and 3) tap water heating. In addition to providing additional heating capabilities, the heat energy generated by the system may be easily diverted between the indoor air heating system, the hydronic floor heating system and the water heater to provide maximum comfort and energy utilization, store energy for later use and address fluctuations in the energy output of the system.
The system utilizes a novel control system that: 1) prevents unsafe operating parameters; 2) ensures comfortable indoor heating and cooling; 3) utilizes any excess energy present in the system, or stores that energy for later use, by diverting the energy to the hydronic floor heating system and/or the water heater and 4) provides for long run times of the system at optimal conditions to prevent unnecessary and intermittent start up of the compressors.
The system further includes a backup heating source that is effectively integrated and controlled by the system. Load Management Control is also provided so that the system may be shut down remotely by a utility company.
BRIEF DESCRIPTION OF THE DRAWINGSFIG. 1 is a schematic of the preferred embodiment of the heating and cooling system of the present invention.
FIG. 2(a) is a schematic of the System Control of the present invention.
FIG. 2(b) is a schematic showing the interaction of the Heat Pump Manager with System Control of the present invention.
FIG. 3 is a chart showing the decision process employed by System Control when it receives a call for heat from the indoor thermostat when the outdoor ambient temperature is high.
FIG. 4 is a chart showing the decision process employed by System Control when it receives a call for heat from the indoor thermostat when the outdoor ambient temperature is medium.
FIG. 5 is a chart showing the decision process employed by System Control when it receives a call for heat from the indoor thermostat when the outdoor ambient temperature is low.
DETAILED DESCRIPTIONFIG. 1 is a schematic of one embodiment of the heating andcooling system10 of the present invention. The primary components of the system include aprimary compressor12, abooster compressor14, afirst condenser16, asecond condenser18, athird condenser20, aneconomizer22, anevaporator24 and a 4-way valve26.
Theprimary compressor12 is preferably a scroll-type two-speed compressor that may be operated at two discrete discharge pressure settings. Thebooster compressor14 is preferably a single-speed compressor that may be operated at a single discharge pressure setting. The two compressors may be operated in series or thebooster compressor14 may be bypassed by opening boostercompressor bypass valve28. A temperature sensor (HIT) monitors the temperature and a pressure sensor (HI) monitors the pressure of the refrigerant exiting theprimary compressor12.
In the preferred embodiment of the present invention, and depending upon the heating and cooling demands on the system, the system is operated in one of three compressor output modes. First, theprimary compressor12 may be operated at low output. Second, theprimary compressor12 may be operated at high output. Third, both thebooster compressor14 and theprimary compressor12 may be operated with the primary compressor operating at high output. These compressor output modes and the system controls that determine which mode to utilize at any given time will be described in detail below.
Compressed refrigerant from the compressors is directed to thethird condenser20 on the compressor side of system. In thethird condenser20, the high-pressure condensed refrigerant transfers heat to water that is circulated by awater heater pump30 to awater heater32. Thewater heater32 utilizes the heat from thethird condenser20 to heat tap water for home or business use. Thewater heater32 also includes aconventional heating element34 that may also be used to heat the tap water. A temperature monitor (WH-RT)116 senses the temperature of the water returning to thethird condenser20 from thewater heater32. Because thethird condenser20 is located on the compressor side of the 4-way valve26, the third condenser may provide heat for water heating regardless of whether the system is in heating or cooling mode.
In heating mode, the refrigerant flows from the 4-way valve26 to thefirst condenser16, which provides heat for a hydronicfloor heating system36. Abuffer tank pump38 circulates water through thefirst condenser16 and draws heat from the refrigerant to heat the water stored in abuffer tank40. A hydronic floorheating system pump42 circulates the heated water from thebuffer tank40 to a hydronic loop43 to heat the floor of an indoor space. Additional hydronic circuits with independent pumps or zone valves may also be provided to supply additional zones with hydronic heating from the buffer tank. A temperature monitor (WIT)114 senses the temperature of the water in thebuffer tank40. A temperature monitor (W-ST)115 monitors the temperature of the water circulated through thefirst condenser16.
In certain installation configurations where the hydronic floor has sufficient capacity (minimum radiant floor size of at least 35,000 Btu/hr, or approximately 1800 sq. ft.), thebuffer tank40 may not be required. In these installations, the hydronic floor system water may be circulated in direct heat exchange relationship with thefirst condenser16 to provide heat for the hydronic floor system without the need for a buffer tank. In this arrangement, theWIT114 and W-ST115 temperature monitors are placed in the same hot water pipe.
After the first condenser, the refrigerant flows to asecond condenser18, which provides air heating for an indoor space. Although referred to herein as a “condenser,” which is the function it performs in heating mode, thesecond condenser18 operates as an evaporator in cooling mode. Ablower44 directs air over thesecond condenser18 and draws heat from the refrigerant. Theblower44 is preferably a forced air ECM variable speed blower. A temperature monitor (ST)111 senses the temperature of the air being heated by thesecond condenser18.
After thesecond condenser18, the refrigerant flows to areceiver50 and then to aneconomizer22. After theeconomizer22, a portion of the refrigerant flow may be diverted through anexpansion valve46 and back to theeconomizer22 in heat exchange relationship with original refrigerant flow. The diverted flow then flows from theeconomizer22 to a mixingchamber48 on the compression side of the system where the two phase refrigerant is mixed with superheated vapor leaving thebooster compressor14 prior to entering theprimary compressor12.
The remainder of the refrigerant flows to theevaporator24 where a fan51 blows air over theevaporator24 to draw heat into the system. Although referred to herein as an “evaporator,” which is the function it performs in heating mode, the evaporator operates as a condenser in cooling mode. A temperature monitor (OT)110 senses the outdoor temperature at the outdoor evaporator. A temperature monitor (ET) also senses the evaporating temperature of the refrigerant at the evaporator.
After theevaporator24, the refrigerant flows through the 4-way valve26 and back to the compression side of the system to repeat the cycle. An oil filtering and equalization system is also provided on the compression side of the system. Refrigerant leaving the compressors may have oil from the compressors entrained in the refrigerant which will degrade system performance. The oil is separated from the refrigerant by anoil separator52 andoil filter54 and returned to the suction side of theprimary compressor12 at point56 to guarantee lubrication for the compressor.
Oil may also tend to migrate from one compressor to the other depending on the operating conditions of the system. To address oil migration, anoil equalization valve58 is provided that is opened in certain conditions when the compressors are turned off to allow the oil level between the compressors to equalize. Anaccumulator60 is also provided that regulates refrigerant flow to the compressors and protects the compressors from damage during startup.
An auxiliary120 (FIG. 2(a)) or backup electric resistance heating system is also provided that may be used when the primary system components cannot provide adequate heating in extreme cold conditions or to remove load from the compressors under any operating conditions. If a remote utility Load Management Control receiver is implemented with the present system, as described in detail below, a heating system with a different energy source, such as a gas furnace, may also be provided so that the system may utilize this alternative energy heat source when shut down by the Load Management Control receiver.
In cooling mode, only theprimary compressor12 is operated, and it may be operated at either high or low capacity. At the 4-way valve26, the direction of flow is reversed so that the compressed refrigerant flows in the opposite direction on the heat exchange side of the system. Thus, the compressed refrigerant flows from the 4-way valve26 to the evaporator24 (now operating as a condenser) where heat is released to the outdoors. The refrigerant then flows to the second condenser18 (now operating as an evaporator) and the refrigerant draws heat from the indoor air space. In cooling mode, thefirst condenser16 is bypassed by openingvalve62 and closingvalve64, and refrigerant flows from thesecond condenser18 to the 4-way valve26 and back to the compression side of the system to repeat the cycle.
Defrost mode is similar to cooling mode, except that thefirst condenser16 is not bypassed. When the system is in heating mode and the outdoor evaporator requires defrosting, the 4-way valve26 is reversed and compressed refrigerant is circulated to theevaporator24 to defrost the coil. The refrigerant then flows to thesecond condenser18, where theblower44 is turned off, and then to thefirst condenser16. To direct the flow of the refrigerant to thefirst condenser16,valve62 is closed andvalve64 is opened. A temperature monitor (FT) senses the temperature of the refrigerant entering thefirst condenser16. At thefirst condenser16, the refrigerant draws heat from the water circulating to the hydronic floorheating buffer tank40. The refrigerant then flows through the 4-way valve26 and back to the compression side of the system to repeat the cycle. Thus, the heat from thefirst condenser16 is delivered to theevaporator24 to defrost the coil. When defrosting is completed, the system returns to heating mode.
As described above, the heating andcooling system10 of the present invention includes temperature sensors throughout the system. The system also includes sensors that can shut off electrical power to one or both of the compressors under certain conditions. A mechanical safety sensor (HP)68 detects the pressure of the refrigerant leaving theprimary compressor12 and will shut off the compressors if the pressure exceeds a certain maximum. Similarly, a mechanical disk thermostat (HT)70 detects the temperature of the refrigerant leaving theprimary compressor12 and will shut off the compressor if the temperature exceeds a certain maximum. Additional pressure sensors are also located throughout the system and continuously monitor the pressure at various points in the system.
The preferred embodiment of the system includes an indoor thermostat112 (AIR-W, AIR-Y or AIR-G) that is a conventional, 4-wire, RWGY thermostat with a single-step setting for heat (AIR-W) and a single-step setting for cooling (AIR-Y). If set to heating, the indoor thermostat monitors the temperature of the indoor air space and calls for heating (AIR-W) at a temperature set at the thermostat. If set to cooling, theindoor thermostat112 monitors the temperature of the indoor air space and calls for cooling (AIR-Y) at a temperature set at the thermostat.
The hydronicfloor heating system36 includes a thermostat (LOOP-W)113 (FIG. 2(a)). This thermostat monitors the temperature of the hydronicfloor heating system36 and activates thepump42 when the hydronic floor system requires heat. Upon request from the thermostat (LOOP-W)113, thepump42 circulates heated water from thebuffer tank40 to thehydronic floor system36.
FIG. 2(a) is a schematic of the control system of the present invention. The primary inputs to theSystem Control100 are received from an outdoor temperature monitor (OT)110, an air supply temperature monitor (ST)111, anindoor thermostat112, LOOP-W113, a temperature monitor for the water in the buffer tank (WIT)114, a temperature monitor for the water in first condenser (W-ST)115, a temperature monitor for the water in the third condenser (WH-RT)116, theutility load management117, thestandby heat121 and the Heat Pump Manager (HPM)102 (collectively, “the inputs”). The primary outputs from thesystem control100 may be sent to theECM Blower44, thebuffer tank pump38, thewater heater pump30, theHPM102, thestandby heat121, theauxiliary electric120 and the water heater32 (collectively, “the outputs”).
TheSystem Control100 receives inputs from the monitoring devices throughout the system, processes these signals, and makes a “request” to the Heat Pump Manager (HPM)102 for an operational compressor sequence. As will be described in detail below, theSystem Control100 is designed to maximize system efficiency. Through use of decision tables, theSystem Control100 processes the inputs to control the outputs so that excess energy may be transferred within the system for maximum performance.
FIG. 2(b) is a schematic showing the interaction of theHeat Pump Manager102 withSystem Control100 of the present invention. This schematic shows the interconnectivity between theSystem Control100 and theHPM102 and the various components of the present invention. The various components include theSystem Control100, the Heat Pump Manager (HPM)102, thestandby heat121, theutility load management117, theoutdoor unit25, thewater heater32, therelays125, theblower44, thelimits127 and thecompressors126. Theoutdoor unit25 includesevaporator24, fan51 and temperature monitor ET (as shown inFIG. 1).Relays125 include thebuffer tank pump38, thewater heater pump30, theauxiliary heat120 and thewater heater32.
As shown inFIG. 2(b), theHPM102 communicates with thecompressors127, which includes theprimary compressor12 and thebooster compressor14. Furthermore, theHPM102 utilizes theLimits127, which includes high pressure (HP)68 and high temperature (HT)70 within the system. TheHPM102 monitors theLimits127 to ensure safe operating conditions and system efficiency.FIG. 2(b) also shows theHPM102 interacting with theoutdoor unit25. When the defrost mode is activated, theHPM102 controls theoutdoor unit25, thecompressors126 and thelimits127 as will be further described below.
In the preferred embodiment of the present invention,System Control100 andHPM102 are separate computers or controllers. However, the functions ofSystem Control100 andHPM102 may be integrated into a single computer or controller and remain within the scope of the present invention.
TheHPM102 may override or modify the operating parameters set by theSystem Control100 based on additional calculations performed by theHPM102 and/or preset operating limits for certain system components. TheHPM102 thus sets the “actual,” or real time, stage code for the system and prevents unsafe or less than optimal operating conditions.
The system uses eight Stage Codes that correspond to certain operating configurations for the compressors:
|
| 0 | System is off |
| 1 | Heat - primary compressor on low |
| 2 | Heat - primary compressor on high |
| 3 | Heat - primary compressor on high, booster compressor on |
| 4 | Add Load capacity |
| 5 | Cool - primary compressor on low |
| 6 | Cool - primary compressor on high |
| 7 | System hold - safety or performance interrupt |
|
The system is activated when theindoor thermostat112 calls for heating (AIR-W) or cooling (AIR-Y), or when thebuffer tank40 requires heating. When the indoor thermometer calls for heating (AIR-W), theSystem Control100 determines a Request Stage Code andindoor air blower44 speed based on the outdoor temperature (OT). In the figures, a symbol (e.g., “OT”) together with a reference number is used to designate the temperature monitor. However, when the symbol alone is used, the symbol designates the temperature readout on the corresponding temperature monitor. Thus, for example,OT110 designates the outdoor temperature monitor and “OT” alone designates the temperature readout from the outdoor temperature monitor.
If the outdoor temperature (OT) is high (>500),System Control100 requests Stage Code 1 (primary compressor12 on low) from theHPM102 and sets theindoor air blower44 speed to low. If the outdoor temperature (OT) is medium (<55° F. and >20° F.),System Control100 requests Stage Code 2 (primary compressor12 on high) and sets theindoor air blower44 speed to medium. If the outdoor temperature (OT) is low (<20° F.),System Control100 requests Stage Code 3 (primary compressor12 on high andbooster compressor14 on) and sets theindoor air blower44 speed to high.System Control100 then controls theblower44, thebuffer tank pump38, thewater heater pump30 and potentially the auxiliary heating elements according to the decision tables shown inFIGS. 3-5.
Thus, based on the outdoor temperature,System Control100 sets the indoor air blower speed and the output of the compressors, which in turn determine the BTU delivery into the indoor air space. Although the outdoor temperature determines the initial blower and compressor settings,System Control100 may then alter these parameters, along with BTU delivery to thebuffer tank40 and thewater heater32, to maximize indoor air comfort and system efficiency. If the indoor air thermostat (AIR-W) is not satisfied after a preset time,System Control100 may increase the blower speed and increase the Request Stage Code to theHPM102 for the compressors. If both theblower44 and thecompressors126 are in highest output mode and theindoor air thermostat112 remains unsatisfied,System Control100 may add auxiliary heating to satisfy theindoor air thermostat112 call for heat.
To maximize system efficiency,System Control100 monitors the air supply temperature (ST) at theindoor blower44. If ST is either too low to heat the indoor air space or too high for efficient compressor operation,System Control100 may either change the Request Stage Code for the compressors or activate or deactivate thebuffer tank pump38 and/or thewater heater pump30.
For best system efficiency,System Control100 attempts to keep thebuffer tank pump38 and thewater heater pump30 running to utilize any excess energy within the system. Also, by diverting energy to thebuffer tank40 and thewater heater32 whenever possible, compressor run time is increased, which decreases the wear and tear on the compressors caused by frequent start ups. Thus, whenever ST appears to be sufficient to satisfy the call for heat, thebuffer tank pump38 and thewater heater pump30 are activated or kept running. However, if ST goes low, thebuffer tank pump38 and/or thewater heater pump30 may be deactivated so that sufficient energy is available for heating the indoor air space.
The decision steps utilized bySystem Control100 after receiving a call for heat from the indoor air thermostat112 (AIR-W) are shown inFIGS. 3-5. Within these tables, “ST” is the temperature of the air being heated by thesecond condenser18 at theindoor air blower44. In the ST columns, L, M, H are low, medium and high set points for the ST temperature, which are preferably set at 92° F., 96° F. and 102° F. respectively. The “−” and “+” signs refer to the ST temperature dropping below (“−”) or rising above (“+”) the associated set point.
“Timer” is an internal timer in theSystem Control100 that measures the length of time since theindoor thermostat112 has called for heat, thus providing a measure of time since theindoor thermostat112 has remained unsatisfied. MU1 is a shorter timer, preferably 15 minutes, and MU2 is a longer timer, preferably 45 minutes.
“W-ST” is the temperature of the water circulated to thebuffer tank40 by thebuffer tank pump38. If this temperature exceeds a certain set point, preferably 105° F., the system attempts to divert heat from thebuffer tank40.
“Blower” is the forced air ECM variable speedindoor air blower44. The air blower speed (L, M or H), which is set bySystem Control100, determines BTU delivery into the indoor air space (BTU=1.08×CFM×temperature differential).
“Aux” is anauxiliary heating system120 that may be activated if heating requirements cannot be met by the system. Theauxiliary heating system120 may be any type of alternative heating component or system including an electrical resistance heater, a gas furnace or other type of heating. Auxiliary heating may be provided at low (EL1) or high (EL2) output.
“Tank pump” is thebuffer tank pump38. Thebuffer tank pump38 is activated whenever possible to divert energy to thebuffer tank40, and also as a control mechanism to address high temperature and pressure conditions in the system.
“WH Pump” is thewater heater pump30. As explained below, the water heater pump is nearly always set to “ON” whenever the system is running so that heat may be provided to thewater heater32 for water heating. However, when additional heat is needed to heat the indoor air space, or if the temperature water circulated to thewater heater32 exceeds a certain temperature, preferably 135° F., thewater heater pump30 may be deactivated.
“Stage Code” is the Stage Code requested bySystem Control100, which may be modified by theHPM102 as will be described in detail below.
WithinFIGS. 3-5, the “+” symbol means that the system component is activated and the “−” symbol means that the system component is deactivated. “ON” or “OFF” means that the system component is already on or off, or, in some instances, is turned on or off in that decision step. The asterisk “*” symbol indicates a system parameter that is monitored and may trigger the activation or deactivation of a system component. “IF” indicates a system parameter that is monitored and must be satisfied to allow the activation or deactivation of a system component. After activating or deactivating a system component as shown inFIGS. 3-5,System Control100 waits two minutes before making further system changes as provided in the tables.
Referring toFIG. 3, when theSystem Control100 receives a call for heat from the indoor air thermometer (AIR-W) and the outdoor temperature (OT) is high (>55° F.),System Control100 activates theindoor air blower44 on low speed and requests Stage Code 1 (primary compressor12 on low) from theHPM102, as shown inLine1.System Control100 then monitors the system parameters to determine if changes to the system should be made to increase the BTU's delivered to the indoor air space or to improve system performance and efficiency.
As shown inLine2 ofFIG. 3, if the temperature of the air at the indoor air blower (ST) exceeds the medium set point,System Control100 activates thebuffer tank pump38 to divert energy to thebuffer tank40. As shown inLine3, if ST falls below the low temperature set point, meaning that energy is needed to heat the indoor air space, thebuffer tank pump38 is terminated. If the temperature of the water being circulated to the buffer tank exceeds 105° F., as shown inLine4, the blower speed is increased to medium to divert energy to the indoor air space. If ST exceeds the high temperature set point or the water being circulated to the buffer tank exceeds 105° F., as shown inLine5, the indoor blower is set to high to divert additional energy to the indoor air space. If theindoor thermostat112 remains unsatisfied after 45 minutes (MU2), as shown inLine6,System Control100 sets the blower speed to high and requests Stage Code 2 (primary compressor12 set to high) from theHPM102.
Referring toFIG. 4, when theSystem Control100 receives a call for heat from the indoor air thermometer (AIR-W) and the outdoor temperature (OT) is medium (<55° F. and >20° F.),System Control100 activates theindoor air blower44 on medium speed and requests Stage Code 2 (primary compressor12 on high) from theHPM102, as shown inLine7. Then, as shown inLine8, if the temperature of the air at the indoor air blower (ST) exceeds the medium set point,System Control100 activates thebuffer tank pump38 to divert energy to thebuffer tank40. As shown inLine9, if ST falls below the low temperature set point, thebuffer tank pump38 is terminated. If the temperature of the water being circulated to thebuffer tank40 exceeds 105° F., as shown inLine10, the blower speed is increased to high to divert energy to the indoor air space. If theindoor thermostat112 remains unsatisfied after 45 minutes (MU2), as shown inLine11,System Control100 sets the blower speed to high and requests Stage Code 3 (primary compressor12 set to high andbooster compressor14 activated) from theHPM102.
Referring toFIG. 5, when theSystem Control100 receives a call for heat from the indoor air thermometer (AIR-W) and the outdoor temperature (OT) is low (<20° F.),System Control100 activates theindoor air blower44 on high speed, requests Stage Code 3 (primary compressor12 on high and booster compressor activated) from theHPM102 and leaves thewater heater pump30 off, as shown inLine12.System Control100 then steps down the table in progressive steps as needed.
As shown inLine13, if the temperature of the air at the indoor air blower (ST) exceeds the high set point,System Control100 activates thewater heater pump30 to divert energy to thewater heater32 to provide heat for water heating. As shown inLine14, if ST then falls below the medium temperature set point, thewater heater pump30 is terminated. As shown inLine15, if ST exceeds the high set point,System Control100 activates both thebuffer tank pump38 and thewater heater pump30. As shown inLine16, if ST drops below the medium set point when both thebuffer tank pump38 and thewater heater pump30 are running, both are deactivated. Referring toLine17, if the temperature of the water being circulated to thebuffer tank40 exceeds 105° F., thebuffer tank pump38 and thewater heater pump30 are activated. Referring toLine18, if the indoor thermostat remains unsatisfied after 15 minutes (MU1) with the ST temperature below the high set point, auxiliary heating is activated at low output and thebuffer tank pump38 is activated. Referring toLine19, if the addition of the low output auxiliary heating fails to satisfy theindoor thermostat112 after 45 minutes (MU2), high output auxiliary heating is activated and thebuffer tank pump38 is deactivated. Finally, as shown inLine20, if the ST temperature exceeds the high set point, both thebuffer tank pump38 and thewater heater pump30 are activated.
The system may also be activated when thebuffer tank40 requires heating. As noted above, the hydronicfloor heating system36 includes a thermostat (LOOP-W)113 that activates thepump42 and notifiesSystem Control100 when the hydronic loop43 requires heat.System Control100 then waits three minutes. This delay allows the water to circulate from thebuffer tank40 to the hydronic loop43 before determining whether thebuffer tank40 requires heating. The delay also gives the system time to potentially divert excess energy to thebuffer tank40 under normal operation of the system, thereby avoiding premature, unnecessary and intermittent start up of the compressors. After three minutes,System Control100 continuously monitors the temperature of the water in thebuffer tank40 throughWIT114.
If WIT is below a predetermined point, meaning that thebuffer tank40 requires heating,System Control100 checks whether AIR-W is ON, which would indicate that the indoor air space requires heating. If AIR-W is ON, indoor air heating takes precedence over hydronic floor heating andSystem Control100 continues to follow the decision steps detailed above. If AIR-W is OFF after the delay, meaning that the indoor air space does not require heating,System Control100 may then activate thebuffer tank38 to provide heat to thebuffer tank40.
With respect to the interaction ofSystem Control100 with thewater heater32, the goal of the system is to utilize thethird condenser20 rather theelement34 to heat the water in thewater heater32 because the heat pump provides more efficient heating that the heating element of a conventional water heater. To achieve this goal, the water heater pump30 runs under most conditions when theprimary compressor12 or both compressors are running. When the system is active, theelement34 is interrupted whenever possible so that thethird condenser20, rather than thewater heater element34, is providing energy to the water heater.
However, when the outdoor temperature is very low and energy is needed to heat the indoor air space, thewater heater pump30 is interrupted or left off. As shown inFIG. 5 atline12, thewater heater pump30 is left off when the system is activated upon a call for heat at a low outdoor temperature. As shown inFIG. 5 atlines14 and16, thewater heater pump30 is deactivated when the temperature of the air at the indoor air blower (ST) drops below the medium temperature set point. As shown inFIG. 5 atlines18 and19, thewater heater pump30 is not run when theindoor air thermostat112 is not satisfied after either the short (MU1) or longer (MU2) time period. Thewater heater pump30 is also interrupted when the temperature of the water circulating to the water heater (WH-RT) exceeds a certain temperature (125°). (However, whenStage Code 4 is activated as explained below, thewater heater pump30 is activated despite the high temperature of WH-RT.) Theelement34, of course, provides heat for water heating whenever the system is not running. To achieve the goal of utilizing heat from thethird condenser20 rather than theelement34 whenever possible, theelement34 is interrupted whenever the system starts or stops. A timer is then started. At the expiration of the timer, theelement34 then is allowed to decide for itself based on its own thermometer whether to turn on and heat the water in thewater heater32.
When the system starts, a shorter timer (30 minutes) is started. Under normal conditions with the heat pump running, the heat pump should provide sufficient energy to heat the water in thewater heater32 within this time period so that, at the expiration of the timer, theelement34 will not need to provide heating. However, if a significant amount of hot water is being used, theelement34 may provide additional heating at the expiration of the timer.
When the system stops, a longer timer (120 minutes) is started. This timer prevents theelement34 from activating at the end of a heat pump cycle when the system may be restarting within a short time period. If the system does not restart, however, heating control is returned to the element and the conventional water heater thermostat.
The element deactivation timer at system shutdown should typically be longer than the element deactivation timer at system startup. At system startup, the system is providing heat to the water heater. The timer may be shorter so that the element can determine whether supplemental heating is required, such as, for example, when someone is draining the hot water and the heat pump cannot keep up. The inventor currently contemplates setting the shutdown timer at 120 minutes and the startup timer at 30 minutes, but these settings depend on the water heater tank size, household domestic hot water use and other factors.
Element interrupts may also be incorporated based on the outside air temperature (OT). At temperatures above 0° F., the heat pump system should provide sufficient heating for water in thewater heater32 under all system conditions so that element heating is never required. At temperatures below 0° F., however, the system may require that energy be diverted from thewater heater32 to the indoor air space for to satisfy indoor air comfort requirements. As a result, element heating of the water for domestic use may be more frequently required. Thus, at low outdoor temperatures, theelement34 is not interrupted and the element is free to cycle on its own internal thermostat.
As noted above, theHPM102 may override the system parameters set bySystem Control100 and provide internal control of the system components and compressors. These overrides may occur to prevent unsafe operating conditions or to increase the operating efficiency of the system.
First, whenever the system generates a high pressure68 (HP) greater than 420 psig or a high temperature70 (HT) greater than 200° F. at the outlet of the primary compressor, theHPM102 overrides whatever Request Stage Code has been determined bySystem Control100 and activatesStage Code 4.Stage Code 4 activates thebuffer tank pump38 and thewater heater pump30 for thirty seconds if they are not already activated. Activation of these pumps draws energy from the system in an attempt to prevent the pressure and temperature from going over limit and utilizes this excess energy for the hydronicfloor heating system36 and/or thewater heater32. Thus,Stage Code 4 operates as a safety control while simultaneously increasing the efficiency of the system.
Second, theHPM102 constantly calculates a high side/low side (HI/LO) pressure ratio to further control the system. For the high side pressure, theHPM102 reads the pressure transducer at the outlet of the primary compressor (HP). For the low side pressure, theHPM102 reads the temperature at the evaporator (ET) and converts this reading to pressure using the formula P=A+BT+CT2+DT3where P=pressure [bar], T=temperature [K] and A, B, C & D are constants (For R410A: A=−195.3, B=2.58, C=−0.01165 and D=18.02E-6).
Using this HI/LO pressure ratio, ifSystem Control100requests Stage Code 1 operation and the pressure ratio is greater than 5.5 (averaged over 10 seconds), theHPM102 converts to StageCode 2 and operates theprimary compressor12 at high speed. IfSystem Control100requests Stage Code 2 operation and the pressure ratio is greater than 6.5 (averaged over 10 seconds), theHPM102 converts toStage Code 3 operation and activates thebooster compressor14.
Third, theHPM102 monitors the evaporating temperature of the refrigerant at the evaporator (ET) at all times to ensure that the compressors are always running in an efficient mode. Based on input from ET, the HPM may override a stage code request from System Control that would place the system in an inefficient operating mode.
Fourth, as safety controls, theHPM102 will decrease the Stage Code (converting fromStage Code 3 to 2, or fromStage Code 2 to 1) if the system generates a pressure (HI) greater than 500 psig or a temperature (HIT) greater than 220° at the outlet of the primary compressor. Thus, theHPM102 attempts to address a high pressure or high temperature condition by reducing the output of the compressors before taking more drastic steps.
As further safety controls, if the system generates a pressure (HI) greater than 520 psig or a temperature (HIT) greater than 230° F. at the outlet of the primary compressor, theHPM102 performs a “soft hold,” which is an auto reset of the system. Under this condition, the entire system shuts down, resets and starts up again. TheHPM102 will also perform a soft hold if the primary compressor exceeds 30A during a heating cycle or if the amps of the primary compressor increase more than 30% in 10 seconds. A soft hold may also be initiated in defrost mode if the temperature (FT) of the refrigerant entering thefirst condenser16 is below a predetermined point to prevent potential freeze-up during defrost. The system hardware may also perform a “hard hold,” or complete system shut down, if the system generates a pressure (HP) greater than 600 psig or a temperature (HT) greater than 250° F. at the outlet of the primary compressor. TheHPM102 will also perform a hard hold if three soft hold restarts occur within 12 hours.
In addition to controlling the system compressors to maximize the efficiency and safety of the system, theHPM102 also controls theeconomizer22 to further optimize performance of the system. TheHPM102 precisely regulates the flow of refrigerant through theeconomizer22 based on the temperature or pressure of the refrigerant leaving theprimary compressor12. Starting at 440 psig (HI), theHPM102 opens theexpansion valve46 2% to provide a flow of refrigerant through the economizer. Then, for each increase in pressure of 4 psig, theHPM102 opens theexpansion valve46 an additional 2%. Thus, for example, at 460 psig, a 22% injection flow is provided. TheHPM102 also reads the temperature at the primary compressor outlet (HIT) and, starting at 170°, opens thevalve46 diverting flow to theeconomizer 2% for every 3° increase in temperature. This causes, for example, an injection of 18% at 194° F. The actual injection is the larger of the two percentages that result from the HPM's calculations.
With respect to the control of the system in cooling mode, the system is activated when theindoor thermostat112 calls for cooling. In cooling mode, thebooster compressor14 is not used. Theprimary compressor12 is used at low speed (Stage Code 5) or high speed (Stage Code 6) if additional cooling capacity is required.Stage Code 6 may be activated after a predetermined time, preferably 90 minutes, ifStage Code 5 fails to satisfy the thermostat (AIR-Y).
In cooling mode, all pressure and temperature calculations are disabled. However, theHPM102 will convert fromStage Code 6 operation to StageCode 5 operation if the system generates a pressure (HP) greater than 480 psig or a temperature (HT) greater than 200° F. at the outlet of the primary compressor. TheHPM102 will also perform a soft hold if the temperature at the outlet of the primary compressor (HIT) exceeds 230° F., theprimary compressor12 exceeds 30A during a heating cycle or the amps of the primary compressor increase more than 20% in 20 seconds. The safety settings for a hard hold also remain active.
TheHPM102 may activate the defrost mode one of three ways. First, if the outside temperature (OT) has been 40° F. or less for 2 hours of cumulative system run time or 15° F. or less for 4 hours of cumulative system run time, the defrost cycle is activated. Second, theevaporator24 includes a pressure differential switch that may activate the defrost cycle. Third, the defrost cycle may be manually activated. During a defrost cycle, the system disables all compressor, pressure and staging calculations and decisions.
When defrost mode is activated, thecompressors12 and14 and the outdoor fan51 are turned off and thebuffer tank pump38 is activated. After thirty seconds, the 4-way valve26 is reversed and theprimary compressor12 is activated. As described above, the refrigerant then flows through thefirst condenser16 to transfer heat from thebuffer tank40 to the refrigerant that is cycled to theevaporator24 to defrost the coil. At the end of the defrost cycle, the outdoor fan51 is turned back on, the 4-way valve26 is reversed and thebuffer tank pump38 is turned off or allowed to return to whatever mode it was in prior to the defrost cycle.
The present invention is also compatible and easily integrated with utility Load Management Control. Load Management Control, or LMC, allows a utility company to remotely and temporarily shut down certain users' heating and cooling systems at times when the utility is experiencing peak loads. This flexibility in addressing peak load conditions is a great advantage to utility companies. In exchange for the right and ability to remotely shut down a user's heating and cooling system, a utility company will typically provide reduced electricity rates, which is of course an advantage to the consumer.
To enable the Load Management Control function, the system includes a remote receiver or communication device provided by the utility company. The utility company may communicate with the remote receiver via a telephone line, radio waves, the internet or other means. The remote receiver is integrated withSystem Control100 so that, when the remote receiver receives a signal from the utility company, the remote receiver instructsSystem Control100 to place the heating and cooling system on standby.System control100 then shuts down the system (including any auxiliary electrical heating) for a set period of time, or until a restart signal is received from the utility company through the remote receiver.
Anauxiliary heating system120 with a different energy source, such as a gas furnace, is typically provided to provide heat when Load Management Control initiates a system shut down in cold weather conditions. This backup heating source is an integral part of the system and controlled by theSystem Control100. By providing this control, the system can easily transition to the backup heating source when a shut down command is received, and also easily transition back to the main heating system when the shut down condition terminates.
The present system is designed to provide three outputs-forced air heating and cooling for an indoor air space, water heating for a hydronic heating system and water heating for a conventional tap water heater. As noted above, the novel system configuration and control diverts energy among these three outputs to maximize comfort, increase system efficiency, control high system load conditions, maximize compressor run times and utilize excess system energy. Although the preferred embodiment of the present invention utilizes three outputs to achieve these goals, these goals may also be achieved with only two of the three outputs. Thus, alternative embodiments of the present invention include systems with forced air heating and cooling combined with hydronic floor heating, forced air heating and cooling combined with tap water heating and hydronic floor heating combined with tap water heating.
Other alterations, variations and combinations are possible that fall within the scope of the present invention. For example, as described above, the System Control may be integrated into a single computer or controller and remain within the scope fo the present invention. Although the preferred embodiments of the present invention have been described, those skilled in the art will recognize other modifications that may be made that would nonetheless fall within the scope of the present invention. Therefore, the present invention should not be limited to the apparatus and method described. Instead, the scope of the present invention should be consistent with the invention claimed below.