Vapor barrier

From Wikipedia, the free encyclopedia
Damp proofing material in sheet form
6-mil (0.15 mm)polyethylene plastic sheet as vapour barrier between insulation andgypsum board
Glass wool pipeinsulation covering asteelpipe as it penetrates a mock-upconcrete slab whoseopening will befirestopped. In this manner, the vapor barrier (in this case made of foil/scrim/kraft paper, called ASJ, all-service jacket, aluminium on the inside, white paper on the outside) can remain intact as it penetrates the fire barrier.

Avapor barrier (orvapour barrier) is any material used fordamp proofing, typically a plastic or foil sheet, that resists diffusion of moisture through the wall, floor, ceiling, or roof assemblies of buildings and ofpackaging to preventinterstitial condensation. Technically, many of these materials are onlyvapor retarders as they have varying degrees ofpermeability.

Materials have amoisture vapor transmission rate (MVTR) that is established by standard test methods. One common set of units is g/m2·day or g/100in2·day. Permeability can be reported inperms, a measure of the rate of transfer of water vapor through a material (1.0 US perm = 1.0 grain/square-foot·hour·inch of mercury ≈ 57 SI perm = 57 ng/s·m2·Pa). American building codes started classifying vapor retarders in the 2007 IRC supplement. They are Class I <0.1 perm, Class II 0.1 - 1 perm and Class III 1-10 perm when tested in accordance with the ASTM E96 desiccant, dry cup or method A.[1] Vapor-retarding materials are generally categorized as:

  • Class I, Impermeable (<0.1 US perm, or ≤5.7 SI perm) – such as asphalt-backed kraft paper, glass, sheet metal, polyethylene sheet, rubber membrane, vinyl wall coverings;
  • Class II, Semi-impermeable (0.1-1 US perm, or 5.7-57 SI perm) – such as unfaced expanded or extrudedpolystyrene,OSB, fiber-facedisocyanurate, 30 pound asphalt-impregnated building papers, exterior oil-based paints, unfaced expanded polystyrene, 30 pound asphalt coated paper, plywood, bitumen coated kraft paper;
  • Class III, Semi-permeable (1-10 US perm, or 57-570 SI perm) – such as unfaced expanded polystyrene, fiber-facedisocyanurate,plywood, 15 pound asphalt coated paper, some latex-based paints;
  • Permeable (>10 US perm, or >570 SI perm) – such as unpainted gypsum board and plaster, unfaced fiber glass insulation, cellulose insulation, unpaintedstucco, cement sheathings, spunbondedpolyolefin (building wraps) or some polymer-based exterior air barrier films.

Materials

[edit]

Vapor diffusion retarders are normally available as coatings or membranes. The membranes are technically flexible and thin materials, but sometime includes thicker sheet materials named as "structural" vapor diffusion retarders. The vapor diffusion retarders varies from all kinds of materials and keep updating every day, some of them nowadays even combined the functions of other building materials.

Materials used as vapor retarders:

  • Elastomeric coatings can provide a vapor barrier and water proofing with permeability ratings of .016 perm rating with 10 mils/min. of coating and can be applied on interior or exterior surfaces.
  • Aluminum foil, 0.05 US perm (2.9 SI perm).
  • Paper-backed aluminum.
  • Asphalt orcoal tar pitch, typically hot-applied to concrete roof decks along with reinforcement felts.
  • Polyethylene plastic sheet, 4 or 6 thou (0.10 or 0.15 mm), 0.03 US perm (1.7 SI perm).
  • Advanced Polyethylene vapor retarders that pass the ASTM E 1745 standard tests ≤0.3 US perm (17 SI perm).
  • Asphalt-coatedkraft paper, often attached to one side of fiberglass batts, 0.40 US perm (22 SI perm).
  • Metallized film
  • Vapor retarder paints (for the air-tight drywall system, for retrofits where finished walls and ceilings will not be replaced, or for dry basements: can break down over time due to being chemically based).
  • Extruded polystyrene or foil-faced foam board insulation.
  • Exterior gradeplywood, 0.70 US perm (40 SI perm).
  • Most sheet type monolithic roofing membranes.
  • Glass and metal sheets (such as in doors and windows).

Building construction

[edit]
vapor barrier location by geographical location.
Vapor barrier location by geographical location

Moisture or water vapor moves into building cavities in three ways:1) With air currents, 2) By diffusion through materials, 3) By heat transfer.Of these three, air movement accounts for more than 98% of all water vapor movement in building cavities.[2] A vapor retarder and anair barrier serve to reduce this problem, but are not necessarily interchangeable.

Vapor retarders slow the rate of vapor diffusion into the thermal envelope of a structure. Other wetting mechanisms, such as wind-borne rain,capillary wicking of ground moisture, air transport (infiltration), are equally important.

Usage

[edit]

The industry has recognized that in many circumstances it may be impractical to design and build building assemblies which never get wet. Good design and practice involve controlling the wetting of building assemblies from both the exterior and interior.[3] So, the use of vapor barrier should be taken into consideration. Their use has already been legislated within thebuilding code of some countries (such as the U.S., Canada, Ireland, England, Scotland & Wales). How, where, and whether a vapor barrier (vapor diffusion retarder) should be used depends on the climate. Typically, the number ofheating degree days (HDD) in an area is used to help make these determinations. A heating degree day is a unit that measures how often outdoor dailydry-bulb temperatures fall below an assumed base, normally 18 °C (65 °F).[4] For building in most parts of North America, where winter heating conditions predominate, vapor barrier are placed toward the interior, heated side of insulation in the assembly. In humid regions where warm-weather cooling predominates within buildings, the vapor barrier should be located toward the exterior side of insulation. In relatively mild or balanced climates, or where assemblies are designed to minimize condensation conditions, a vapor barrier may not be necessary at all.[5]

An interior vapor retarder is useful in heating-dominated climates while an exterior vapor retarder is useful in cooling-dominated climates. In most climates it is often better to have a vapor-open building assembly, meaning that walls and roofs should be designed to dry:[6] either to the inside, the outside, or both, so the ventilation of water vapor should be taken into consideration.A vapor barrier on the warm side of the envelope must be combined with a venting path on the cold side of the insulation. This is because no vapor barrier is perfect, and because water may get into the structure, typically from rain. In general, the better the vapor barrier and the drier the conditions, the less venting is required.[7]

In areas below foundation level (subgrade areas), particularly those formed in concrete, vapor retarder placement can be problematic, as moisture infiltration fromcapillary action can exceed water vapor movement outward through framed and insulated walls.

A slab-on-grade or basement floor should be poured over a cross-laminated polyethylene vapor barrier over 4 inches (10 cm) of granular fill to prevent wicking of moisture from the ground and radon gas incursion.

Inside a steel building, water vapor will condense whenever it comes into contact with a surface that is below thedew point temperature. Visible condensation on windowpanes andpurlins that results in dripping can be somewhat mitigated with ventilation; however insulation is the preferred method of condensation prevention.

Confusion with air barrier

[edit]

The function of a vapor barrier is to retard the migration of water vapor. A vapor barrier is not typically intended to retard the migration of air. This is the function ofair barriers.[8] Air is mixed with water vapor. When air moves from location to location due to an air pressure difference, the vapor moves with it. This is a type of migration of water vapor. In the strictest sense air barriers are also vapor barriers when they control the transport of moisture-laden air.[9] It must be mentioned that the designated perm ratings do not reflect the diminished permeability of a given vapor retarder medium when affected by temperature differences on opposing sides of the medium.[10] A discussion about the differences between vapor barriers and air barriers can be found in Quirouette.[11]

Packaging

[edit]
Main articles:Package testing,Moisture vapor transmission rate,Oxygen transmission rate, andCarbon dioxide transmission rate

The ability of a package to control thepermeation and penetration of gasses is vital for many types of products. Tests are often conducted on the packaging materials but also on the completed packages, sometimes after being subjected to flexing, handling, vibration, or temperature.

See also

[edit]

References

[edit]
  1. ^Smart Vapor Retarders. Certain Teed Corporation. 2006. p. 2.
  2. ^US Department of Energy."How Moisture Moves through a Home". Archived fromthe original on December 29, 2010. RetrievedJanuary 1, 2011.
  3. ^Lstiburek, Joseph (2004).Vapor Barriers and Wall Design. Building Science Press. Archived fromthe original on 2015-06-29. Retrieved2011-12-01.
  4. ^U.S. Department of Energy."Vapor Barriers or Vapor Diffusion Retarders". U.S. Department of Energy. Retrieved2011-11-24.
  5. ^Allen, Edward; Iano, Joseph (2013).Fundamentals of Building Construction: Materials and Methods (6th ed.). Wiley.ISBN 978-1-118-42086-7.
  6. ^The Perfect Wall, Roof, and Slab - Building Science Podcast
  7. ^Donald, Wulfinghoff (1999).Energy Efficiency Manual: for everyone who uses energy, pays for utilities, designs and builds, is interested in energy conservation and the environment. Energy InstPr ( March 2000). p. 1393.ISBN 0-9657926-7-6.
  8. ^Lstiburek, Joseph (October 24, 2006).Building Science Digest 106: Understanding Vapor Barriers(PDF). 2006 Building Science Press. Archived fromthe original(PDF) on October 30, 2012. RetrievedDecember 1, 2011.
  9. ^MIDWEST RESEARCH INSTITUTE, ed. (6 April 2004)."5.C.2.1 Vapor Barrier Journal Paper"(PDF): 3. KAAX-3-32443-00. Archived fromthe original(PDF) on 2013-01-08. Retrieved2011-11-29.{{cite journal}}:Cite journal requires|journal= (help)
  10. ^"Vapor Retarders and Barriers".by, Robert Wewer. FSI Restorations. Retrieved1 January 2014.
  11. ^R.L., Quirouette (July 1985). "The Difference Between a Vapor Barrier and an Air Barrier: Building Practice Note 54".Building Practice Note. Ottawa, Ontario, Canada: National Research Council of Canada.ISSN 0701-5216.
  • Fine Homebuilding No. 169 March 2005 p. 78
  • Fine Homebuilding No. 162, May 2004 p. 52

External links

[edit]
Wikimedia Commons has media related toVapor barriers.
Fundamental
concepts
Technology
Components
Measurement
and control
Professions,
trades,
and services
Industry
organizations
Health and safety
See also
Retrieved from "https://en.wikipedia.org/w/index.php?title=Vapor_barrier&oldid=1318470827"
Categories:
Hidden categories:

[8]ページ先頭

©2009-2026 Movatter.jp