This articleneeds additional citations forverification. Please helpimprove this article byadding citations to reliable sources. Unsourced material may be challenged and removed. Find sources: "Expansion tank" – news ·newspapers ·books ·scholar ·JSTOR(September 2018) (Learn how and when to remove this message) |

Anexpansion tank orexpansion vessel is a smalltank used to protect closedwater heating systems and domestic hot water systems from excessive pressure. The tank is partially filled with air, whose compressibility cushions shock caused bywater hammer[citation needed] and absorbs excess water pressure caused bythermal expansion.[1] Larger similar expansion tanks are also used with well water supply systems to reduce excessive On-Off cycling of the well pump when moderate quantities of water are withdrawn from a faucet, and in turn from the expansion tank, without the excessive wear of the well pump to turn on and off for only a few seconds.
The modern vessel is a small container or tank divided in two by a rubberdiaphragm. One side is connected to the pipe work of the heating system and therefore contains water. The other, the dry side, contains air under pressure, and normally aSchrader valve (car-tire type valve stem) for checking pressures and adding air when needed. When the heating system is empty or at the low end of the normal range of working pressure, the diaphragm is pushed against the water inlet; as the water pressure increases, the diaphragm moves, compressing the air on its other side.
An older style of expansion tank was larger, oriented horizontally, and had no rubber diaphragm separating the water from the air pocket. This now-obsolete style would gradually transfer air from the tank to the highest point in the system, due to air dissolving in the water and then coming out of solution elsewhere in the system. This in turn required periodic draining of the expansion tank, as well as periodic bleeding of unwanted air from other sections of the system, to maintain its effectiveness.
The rubber diaphragm in modern expansion tanks prevents this undesired transfer of air, and helps maintain low levels of dissolvedoxygen within the pipes, reducingcorrosion in the system.
When expansion tanks are used indomestic hot water (DHW) systems, the tank and the diaphragm must conform todrinking water regulations and must be capable of accommodating the required volume of water.
In the past, domestic plumbing systems often contained more air than they do currently[citation needed], and the trapped air acted as a crude expansion buffer. In new and upgraded systems, expansion tanks are designed in and installed[2] more frequently than in the past.
In the UK, prior to the use of sealed expansion tanks, "open" tanks were installed in the roof space to accommodate the water's expansion[citation needed]; these had the disadvantage of being exposed to cold air in the roof space. This, without effective loft insulation, could fall below freezing, and could cause the pipework supplying the tank to freeze. However, with good pipe and tank insulation, this was in practice quite rare. Although such systems were remarkably trouble free, there are concerns about the potability of water from roof tanks due to the possibility of contamination. The other major disadvantage is that the water pressure from a roof tank is considerably lower than mains water pressure, making the use ofmixer taps sometimes unpredictable.
Domestichydronic heating and cooling systems generally include an expansion tank to buffer pressure changes due to expansion and contraction of the water used for heat transfer.
A minimum pressure of 28–34 kPa; 0.28–0.34 bar (4–5 psi) at the top of a closed hydronic system is suggested.[3]
In Europe the design and the construction of expansion tanks are ruled by EN 13831 according to Pressure Equipment Directive (PED) 97/23/EC.

An expansion tank, also known as "overflow bottle", is also used in thecooling system of mostinternal combustion engines, to allow the coolant, such asantifreeze, and the air in the system to expand with rising temperature and pressure. The tank is also called a "coolant recovery tank", since it prevents venting and permanent loss of coolant, by allowing it to be sucked back into the cooling system as the engine cools.
Similar devices are used in large-scalepumping stations, where they may be called anexpansion chamber[4] or a hydrophore, to maintain an even pressure and to reduce the effects ofwater hammer.