SCADA (an acronym forsupervisory control and data acquisition) is acontrol system architecture comprisingcomputers, networkeddata communications andgraphical user interfaces forhigh-level supervision of machines and processes. It also covers sensors and other devices, such asprogrammable logic controllers, which interface with process plant or machinery.
The operator interfaces which enable monitoring and the issuing of process commands, such as controllersetpoint changes, are handled through the SCADA computer system. The subordinated operations, e.g. the real-time control logic or controller calculations, are performed by networked modules connected to the fieldsensors andactuators.
The SCADA concept was developed to be a universal means of remote-access to a variety of local control modules, which could be from different manufacturers and allowing access through standard automationprotocols. In practice, large SCADA systems have grown to become similar todistributed control systems in function, while using multiple means of interfacing with the plant. They can control large-scale processes that can span multiple sites, and work over large distances. It is one of the most commonly-used types ofindustrial control systems.
The key attribute of a SCADA system is its ability to perform a supervisory operation over a variety of other proprietary devices.
Level 1 contains theprogrammable logic controllers (PLCs) orremote terminal units (RTUs).
Level 2 contains the SCADA to readings and equipment status reports that are communicated to level 2 SCADA as required. Data is then compiled and formatted in such a way that a control room operator using thehuman-machine interface (HMI) can make supervisory decisions to adjust or override normal RTU (PLC) controls. Data may also be fed to ahistorian, often built on a commoditydatabase management system, to allow trending and other analytical auditing.
SCADA systems typically use atag database, which contains data elements calledtags orpoints, which relate to specific instrumentation or actuators within the process system. Data is accumulated against these unique process control equipment tag references.
A SCADA system usually consists of the following main elements:
An important part of most SCADA implementations isalarm handling. The system monitors whether certain alarm conditions are satisfied, to determine when an alarm event has occurred. Once an alarm event has been detected, one or more actions are taken (such as the activation of one or more alarm indicators, and perhaps the generation of email or text messages so that management or remote SCADA operators are informed). In many cases, a SCADA operator may have to acknowledge the alarm event; this may deactivate some alarm indicators, whereas other indicators remain active until the alarm conditions are cleared.
Alarm conditions can be explicit—for example, an alarm point is a digital status point that has either the value NORMAL or ALARM that is calculated by a formula based on the values in other analogue and digital points—or implicit: the SCADA system might automatically monitor whether the value in an analogue point lies outside high and low- limit values associated with that point.
Examples of alarm indicators include a siren, a pop-up box on a screen, or a coloured or flashing area on a screen (that might act in a similar way to the "fuel tank empty" light in a car); in each case, the role of the alarm indicator is to draw the operator's attention to the part of the system 'in alarm' so that appropriate action can be taken.
"Smart" RTUs, or standard PLCs, are capable of autonomously executing simple logic processes without involving the supervisory computer. They employ standardized control programming languages (such as those underIEC 61131-3, a suite of five programming languages including function block, ladder, structured text, sequence function charts and instruction list), that are frequently used to create programs which run on these RTUs and PLCs. Unlike a procedural language likeC orFORTRAN, IEC 61131-3 has minimal training requirements by virtue of resembling historic physical control arrays. This allows SCADA system engineers to perform both the design and implementation of a program to be executed on an RTU or PLC.
Aprogrammable automation controller (PAC) is a compact controller that combines the features and capabilities of a PC-based control system with that of a typical PLC. PACs are deployed in SCADA systems to provide RTU and PLC functions. In many electrical substation SCADA applications, "distributed RTUs" use information processors or station computers to communicate withdigital protective relays, PACs, and other devices for I/O, and communicate with the SCADA master in lieu of a traditional RTU.
Since about 1998, virtually all major PLC manufacturers have offered integrated HMI/SCADA systems, many of them using open and non-proprietary communications protocols. Numerous specialized third-party HMI/SCADA packages, offering built-in compatibility with most major PLCs, have also entered the market, allowing mechanical engineers, electrical engineers and technicians to configure HMIs themselves, without the need for a custom-made program written by a software programmer. The Remote Terminal Unit (RTU) connects to physical equipment. Typically, an RTU converts the electrical signals from the equipment to digital values. By converting and sending these electrical signals out to equipment the RTU can control equipment.
SCADA systems have traditionally used combinations of radio and direct wired connections, althoughSONET/SDH is also frequently used for large systems such as railways and power stations. The remote management or monitoring function of a SCADA system is often referred to astelemetry. Some users want SCADA data to travel over their pre-established corporate networks or to share the network with other applications. The legacy of the early low-bandwidth protocols remains, though.
SCADA protocols are designed to be very compact. Many are designed to send information only when the master station polls the RTU. Typical legacy SCADA protocols includeModbus RTU,RP-570,Profibus and Conitel. These communication protocols, with the exception of Modbus (Modbus has been made open by Schneider Electric), are all SCADA-vendor specific but are widely adopted and used. Standard protocols areIEC 60870-5-101 or 104,IEC 61850 andDNP3. These communication protocols are standardized and recognized by all major SCADA vendors. Many of these protocols now contain extensions to operate overTCP/IP. Although the use of conventional networking specifications, such asTCP/IP, blurs the line between traditional and industrial networking, they each fulfill fundamentally differing requirements.[3]Network simulation can be used in conjunction with SCADA simulators to perform various 'what-if' analyses.
With increasing security demands (such asNorth American Electric Reliability Corporation (NERC) andcritical infrastructure protection (CIP) in the US), there is increasing use of satellite-based communication. This has the key advantages that the infrastructure can be self-contained (not using circuits from the public telephone system), can have built-in encryption, and can be engineered to the availability and reliability required by the SCADA system operator. Earlier experiences using consumer-gradeVSAT were poor. Modern carrier-class systems provide the quality of service required for SCADA.[4]
RTUs and other automatic controller devices were developed before the advent of industry wide standards for interoperability. The result is that developers and their management created a multitude of control protocols. Among the larger vendors, there was also the incentive to create their own protocol to "lock in" their customer base. Alist of automation protocols is compiled here.
An example of efforts by vendor groups to standardize automation protocols is the OPC-UA (formerly "OLE for process control" nowOpen Platform Communications Unified Architecture).
SCADA systems have evolved through four generations as follows:[5][6][7][8]
Early SCADA system computing was done by largeminicomputers. Common network services did not exist at the time SCADA was developed. Thus SCADA systems were independent systems with no connectivity to other systems. The communication protocols used were strictly proprietary at that time. The first-generation SCADA system redundancy was achieved using a back-up mainframe system connected to all theRemote Terminal Unit sites and was used in the event of failure of the primary mainframe system.[9] Some first generation SCADA systems were developed as "turn key" operations that ran on minicomputers such as thePDP-11 series.[10]
SCADA information and command processing were distributed across multiple stations which were connected through a LAN. Information was shared in near real time. Each station was responsible for a particular task, which reduced the cost as compared to First Generation SCADA. The network protocols used were still not standardized. Since these protocols were proprietary, very few people beyond the developers knew enough to determine how secure a SCADA installation was. Security of the SCADA installation was usually overlooked.
Similar to a distributed architecture, any complex SCADA can be reduced to the simplest components and connected through communication protocols. In the case of a networked design, the system may be spread across more than one LAN network called aprocess control network (PCN) and separated geographically. Several distributed architecture SCADAs running in parallel, with a single supervisor and historian, could be considered a network architecture. This allows for a more cost-effective solution in very large scale systems.
The growth of the internet has led SCADA systems to implement web technologies allowing users to view data, exchange information and control processes from anywhere in the world through web SOCKET connection.[11][12] The early 2000s saw the proliferation of Web SCADA systems.[13][14][15] Web SCADA systems use web browsers such as Google Chrome and Mozilla Firefox as the graphical user interface (GUI) for the operators HMI.[16][13] This simplifies the client side installation and enables users to access the system from various platforms with web browsers such as servers, personal computers, laptops, tablets and mobile phones.[13][17]
SCADA systems that tie together decentralized facilities such as power, oil, gas pipelines, water distribution and wastewater collection systems were designed to be open, robust, and easily operated and repaired, but not necessarily secure.[18][19] The move from proprietary technologies to more standardized and open solutions together with the increased number of connections between SCADA systems, office networks and theInternet has made them more vulnerable to types ofnetwork attacks that are relatively common incomputer security. For example,United States Computer Emergency Readiness Team (US-CERT) released a vulnerability advisory[20] warning that unauthenticated users could download sensitive configuration information includingpassword hashes from anInductive AutomationIgnition system utilizing a standardattack type leveraging access to theTomcatEmbedded Web server. Security researcher Jerry Brown submitted a similar advisory regarding abuffer overflow vulnerability[21] in aWonderware InBatchClientActiveX control. Both vendors made updates available prior to public vulnerability release. Mitigation recommendations were standardpatching practices and requiringVPN access for secure connectivity. Consequently, the security of some SCADA-based systems has come into question as they are seen as potentially vulnerable tocyber attacks.[22][23][24]
In particular, security researchers are concerned about:
SCADA systems are used to control and monitor physical processes, examples of which are transmission of electricity, transportation of gas and oil in pipelines, water distribution, traffic lights, and other systems used as the basis of modern society. The security of these SCADA systems is important because compromise or destruction of these systems would impact multiple areas of society far removed from the original compromise. For example, a blackout caused by a compromised electrical SCADA system would cause financial losses to all the customers that received electricity from that source. How security will affect legacy SCADA and new deployments remains to be seen.
There are many threat vectors to a modern SCADA system. One is the threat of unauthorized access to the control software, whether it is human access or changes induced intentionally or accidentally by virus infections and other software threats residing on the control host machine. Another is the threat of packet access to the network segments hosting SCADA devices. In many cases, the control protocol lacks any form ofcryptographic security, allowing an attacker to control a SCADA device by sending commands over a network. In many cases SCADA users have assumed that having a VPN offered sufficient protection, unaware that security can be trivially bypassed with physical access to SCADA-related network jacks and switches. Industrial control vendors suggest approaching SCADA security likeInformation Security with adefense in depth strategy that leverages common IT practices.[25] Apart from that, research has shown that the architecture of SCADA systems has several other vulnerabilities, including direct tampering with RTUs, communication links from RTUs to the control center, and IT software and databases in the control center.[26] The RTUs could, for instance, be targets of deception attacks injecting false data[27] ordenial-of-service attacks.
The reliable function of SCADA systems in our modern infrastructure may be crucial to public health and safety. As such, attacks on these systems may directly or indirectly threaten public health and safety. Such an attack has already occurred, carried out onMaroochy Shire Council's sewage control system inQueensland,Australia.[28] Shortly after a contractor installed a SCADA system in January 2000, system components began to function erratically. Pumps did not run when needed and alarms were not reported. More critically, sewage flooded a nearby park and contaminated an open surface-water drainage ditch and flowed 500 meters to a tidal canal. The SCADA system was directing sewage valves to open when the design protocol should have kept them closed. Initially this was believed to be a system bug. Monitoring of the system logs revealed the malfunctions were the result of cyber attacks. Investigators reported 46 separate instances of malicious outside interference before the culprit was identified. The attacks were made by a disgruntled ex-employee of the company that had installed the SCADA system. The ex-employee was hoping to be hired by the utility full-time to maintain the system.
In April 2008, the Commission to Assess the Threat to the United States fromElectromagnetic Pulse (EMP) Attack issued a Critical Infrastructures Report which discussed the extreme vulnerability of SCADA systems to an electromagnetic pulse (EMP) event. After testing and analysis, the Commission concluded: "SCADA systems are vulnerable to EMP insult. The large numbers and widespread reliance on such systems by all of the Nation’s critical infrastructures represent a systemic threat to their continued operation following an EMP event. Additionally, the necessity toreboot, repair, or replace large numbers of geographically widely dispersed systems will considerably impede the Nation’s recovery from such an assault."[29]
Many vendors of SCADA and control products have begun to address the risks posed by unauthorized access by developing lines of specialized industrialfirewall andVPN solutions for TCP/IP-based SCADA networks as well as external SCADA monitoring and recording equipment.TheInternational Society of Automation (ISA) started formalizing SCADA security requirements in 2007 with a working group, WG4. WG4 "deals specifically with unique technical requirements, measurements, and other features required to evaluate and assure security resilience and performance of industrial automation and control systems devices".[30]
The increased interest in SCADA vulnerabilities has resulted in vulnerability researchers discovering vulnerabilities in commercial SCADA software and more general offensive SCADA techniques presented to the general security community.[31] In electric and gas utility SCADA systems, the vulnerability of the large installed base of wired and wireless serial communications links is addressed in some cases by applyingbump-in-the-wire devices that employ authentication andAdvanced Encryption Standard encryption rather than replacing all existing nodes.[32]
In June 2010, anti-virus security companyVirusBlokAda reported the first detection of malware that attacks SCADA systems (Siemens'WinCC/PCS 7 systems) running on Windows operating systems. The malware is calledStuxnet and uses fourzero-day attacks to install arootkit which in turn logs into the SCADA's database and steals design and control files.[33][34] The malware is also capable of changing the control system and hiding those changes. The malware was found on 14 systems, the majority of which were located in Iran.[35]
In October 2013National Geographic released a docudrama titledAmerican Blackout which dealt with an imagined large-scale cyber attack on SCADA and the United States' electrical grid.[36]
Both large and small systems can be built using the SCADA concept. These systems can range from just tens to thousands ofcontrol loops, depending on the application. Example processes include industrial, infrastructure, and facility-based processes, as described below:
However, SCADA systems may have security vulnerabilities, so the systems should be evaluated to identify risks and solutions implemented to mitigate those risks.[37]
satellite is a cost-effective and secure solution that can provide backup communications and easily support core smart grid applications like SCADA, telemetry, AMI backhaul and distribution automation
malware (trojan) which affects the visualization system WinCC SCADA.