Movatterモバイル変換


[0]ホーム

URL:


Jump to content
WikipediaThe Free Encyclopedia
Search

Inverter-based resource

From Wikipedia, the free encyclopedia
Source of electricity

Aninverter-based resource (IBR) is a source of electricity that is asynchronously connected to theelectrical grid via an electronicpower converter ("inverter"). The devices in this category, also known asconverter interfaced generation (CIG) andpower electronic interface source, include thevariable renewable energy generators (wind, solar) andenergy storages such as battery, super capacitors, etc..[1][2] These devices lack the intrinsic behaviors (like theinertial response of asynchronous generator) and their features are almost entirely defined by the control algorithms, presenting specific challenges to system stability as their penetration increases,[1] for example, a single software fault can affect all devices of a certain type in acontingency (cf.section on Blue Cut fire below). IBRs are sometimes callednon-synchronous generators.[3] The design of inverters for the IBR generally follows theIEEE 1547 andNERC PRC-024-2 standards.[4]

The term unconventional sources includes IBRs as well as other generators that behave differently than synchronous generators.[5]

Grid-following

[edit]

Agrid-following (GFL) device is synchronized to the local grid voltage and injects an electric current vector aligned with the voltage (in other words, behaves like acurrent source[6]). The GFL inverters are built into an overwhelming majority of installed IBR devices.[1] Due to their following nature, the GFL device will shut down if a large voltage/frequency disturbance is observed.[7] The GFL devices cannot contribute to thegrid strength, dampen active power oscillations, or provideinertia.[8]

Grid-forming

[edit]

Agrid-forming (GFM) device partially mimics certain attributes of a synchronous generator: its voltage is controlled by a locally-controlled oscillator that slows down when more energy is withdrawn from the device.[9] Unlike a conventional generator, the GFM device has noovercurrent capacity and thus will react very differently in theshort-circuit situation.[1] Adding the GFM capability to a GFL device is not expensive in terms of components, but affects the revenues: in order to support the grid stability by providing extra power when needed, the power semiconductors need to be oversized and energy storage added. GFM has higherstandby consumption than GFL.[10] Modeling demonstrates, however, that it is possible to run a power system that almost entirely is based on the GFL devices.[11] A combination of GFMbattery storage power station andsynchronous condensers ("SuperFACTS") is being researched.[12]

European Network of Transmission System Operators for Electricity (ENTSO-E) groups the GFM devices into three classes from 1 to 3, with Class 1 being at the lowest level of contribution to the grid stability (the original classification had the numbers in reverse, with class 1 being the highest). Class 2 is further subdivided in to 2A, 2B, 2C, with 2A being the most basic of the three:[13]

Features

[edit]

Compliance with IEEE 1547 standard makes the IBR to support safety features:[14]

  • if the sensed line voltage significantly deviates from the nominal (usually outside the limits of 0.9 to 1.1pu), the IBR shall disconnect from the after a delay (so calledridethrough time), the delay is shorter if the voltage deviation is larger. Once the inverter is off, it will stay disconnected for a significant time (minutes);
  • if the voltage magnitude is unexpected, the inverter shall enter themomentary cessation state: while still connected, it will not inject any power into the grid. This state has a short duration (less than a second).

Once an IBR ceases to provide power, it can come back only gradually, ramping its output from zero to full power.[15]

The electronic nature of IBRs limits their overload capability: the thermal stress causes their components to even temporarily be able to function at no more than 1-2 times thenameplate capacity, while the synchronous machines can briefly tolerate an overload as high as 5-6 times their rated power.[16]

A typical failure of a conventional synchronous generator (like a loss ofprime mover) is slow (seconds), while the IBR has to disconnect quickly due to low margin for overload.[17]

North American Electric Reliability Corporation (NERC) notes that IBR, like conventional generators, can provideessential reliability services, and summarizes the differences as follows:[18]

Differences between IBRs and synchronous generators
IBRSynchronous generator
Behavior determined by power converter and control softwareBehaviour driven mostly by the physical properties of the machine
Non-existent to small inertiaLarge inertia of the rotor
Lowfault currentHigh fault current
Based on sensitive electronicsDesign can withstand extreme conditions
Fast rampingRamping limited by mechanical limits
Fast frequency controlInertial response by design
Dispatchability limited be environmental conditionsFull dispatchability
Very little plant equipment outside the generatorExtensive auxiliary equipment adding to the risk of tripping

Protection functions

[edit]

The IBR devices come with many protection functions built into the inverters. Experience of the late 2010s and early 2020s had shown that some of these protections are unnecessary, as they were designed with an expectation of astrong grid with little IBR penetration. NERC 2018 guidelines suggested removing some of these checks in order to avoid unnecessary disconnections ("trips") of the IBRs, and newer devices might not have them. The remaining checks are essential for the self-protection of the inverters that, compared to a synchronous generator, have relatively little tolerance for overvoltage and overcurrent.[17] The typical protections include:[19]

  • instant AC overvoltage. A high-amplitudevoltage surge can damage sensitive electronics of the inverter. The voltage sensor measures the waveform with little filtering. In some cases, gating off the inverter during a disturbance can exacerbate the voltage problem (cf.subcycle overvoltage);
  • instant AC overcurrent prevents the inverter, with little tolerance for overload, from feeding the current into a fault. A speedy response is also essential, so very little filtering is applied to the current sensor data;
  • DC overvoltage indicates a problem on the DC bus of the inverter (and a fault internal to the inverter electronics);
  • DC unbalance for multi-level inverter designs (like a 3-levelneutral point clamped, NPC) have multiple DC buses. A voltage imbalance between these buses, that can occur due to waveform distortion caused by an external transient fault, requires a trip to clear;
  • voltage and frequency ride-through disconnect the inverter when a sever waveform distorion is encountered. After the Blu Cut fire incident, the NERC guidelines require the data to be extensively filtered to avoid tripping the device during a short-duration external fault;
  • phase jump protection detects a change in the phase difference between the voltage and current waveforms that might indicate accidentalislanding;
  • loss of synchronism. If the "PLL angle" (an IBR equivalent of therotor angle) changes rapidly, it might indicate malfunctioning of the device, and requires a trip to avoid future damage. However, with weaker grids and high penetration of IBRs, a false alarm is possible.

Once tripped, the IBRs will restart based on a timer or through manual intervention. A typical timer setting is in the seconds to minutes range (theIEEE-1547 default is 300 seconds).[20]

Vulnerabilities

[edit]

New challenges to the system stability came with the increased penetration of IBRs. Incidences of disconnections during contingency events where thefault ride through was expected, and poor damping ofsubsynchronous oscillations inweak grids were reported.[1]

One of the most studied major power contingencies that involved IBRs is theBlue Cut Fire of 2016 inSouthern California, with a temporary loss of more than agigawatt of photovoltaic power in a very short time.[15]

Blue Cut fire

[edit]

TheBlue Cut fire in theCajon Pass on August 16, 2016, has affected multiple high-voltage (500 kV and 287 kV) power transmission lines passing through the canyon. Throughout the day thirteen 500 kVline faults and two 287 kV faults were recorded.[21] The faults themselves were transitory and self-cleared in a short time (2-3.5cycles, less than 60milliseconds), but the unexpected features of the algorithms in the photovoltaic inverter software triggered multiple massive losses of power, with the largest one of almost 1,200megawatts[22] at 11:45:16 AM, persisting for multiple minutes.[23]

The analysis performed by theNorth American Electric Reliability Corporation (NERC) had shown that:

  1. 700 MW of loss were caused by the poorly designed frequency estimation algorithm. The line faults had distorted the AC waveform and fooled the software into a wrong estimate of the grid frequency dropping below 57 Hz, a threshold where an emergency disconnect shall be initiated. However, the actual frequency during the event had never dropped below 59.867 Hz,[24] well above the low limit of the normal frequency range (59.5 Hz for theWestern Interconnection).
  2. Additional 450 MW were lost when low line voltage caused the inverters to immediately cease to inject current, with gradual return to operative state within 2 minutes. At least one manufacturer had indicated that injecting the current when the voltage level is below 0.9pu would involve a major redesign.[25]

As a result of the incident, NERC had issued multiple recommendations, involving the changes in inverter design and amendments to the standards.[4]

References

[edit]
  1. ^abcdeGu & Green 2022, p. 1.
  2. ^ENTSO-E 2020, p. 1.
  3. ^Khan & Minai 2023, p. 1.
  4. ^abNERC 2017, p. 10.
  5. ^Kasztenny 2022, p. 1.
  6. ^Khan & Minai 2023, pp. 1–2.
  7. ^Khan & Minai 2023, p. 4.
  8. ^AEMO 2021, p. 15.
  9. ^Song, Guanhong; Cao, Bo; Chang, Liuchen (March 2022)."Review of Grid-forming Inverters in Support of Power System Operation".Chinese Journal of Electrical Engineering.8 (1):1–15.doi:10.23919/CJEE.2022.000001.ISSN 2836-4619.
  10. ^Heynes, George (2 September 2025)."Grid-forming battery storage: 'Standby consumption will be higher' says Australia's AGL".Energy-Storage.News.
  11. ^Gu & Green 2022, p. 2.
  12. ^Gevorgian, V.; Shah, S.; Yan, W. (2021). "Hybridizing synchronous condensers with grid forming batteries for PV integration – a solution to enhance grid reliability and resiliency".11th Solar & Storage Power System Integration Workshop (SIW 2021). IET Conference Proceedings. Vol. 2021. pp. 85–108.doi:10.1049/icp.2021.2488.ISBN 978-1-83953-680-9.
  13. ^ENTSO-E 2020, pp. 20–21.
  14. ^Popiel 2020, pp. 4–5.
  15. ^abPopiel 2020, p. 5.
  16. ^AEMO 2021, p. 16.
  17. ^abPattabiraman & Inzunza 2024, p. 1.
  18. ^NERC 2023, p. 4.
  19. ^Pattabiraman & Inzunza 2024, pp. 1–2.
  20. ^Pattabiraman & Inzunza 2024, p. 2.
  21. ^NERC 2017, p. v.
  22. ^NERC 2017, p. 2.
  23. ^NERC 2017, p. 5.
  24. ^NERC 2017, p. 8.
  25. ^NERC 2017, p. 9.

Sources

[edit]
Concepts
Portal pylons of Kriftel substation near Frankfurt
Sources
Non-renewable
Renewable
Generation
Failure modes
Protective
devices
Economics
and policies
Statistics and
production
Retrieved from "https://en.wikipedia.org/w/index.php?title=Inverter-based_resource&oldid=1318819021"
Category:
Hidden categories:

[8]ページ先頭

©2009-2025 Movatter.jp