This articleneeds additional citations forverification. Please helpimprove this article byadding citations to reliable sources. Unsourced material may be challenged and removed. Find sources: "Damper" flow – news ·newspapers ·books ·scholar ·JSTOR(September 2014) (Learn how and when to remove this message) |
Adamper is a valve or plate that stops or regulates theflow of air inside aduct,chimney,VAV box,air handler, or other air-handling equipment. A damper may be used to cut off centralair conditioning (heating or cooling) to an unused room, or to regulate it for room-by-roomtemperature andclimate control - for example, in the case of Volume Control Dampers.[1] Its operation can be manual or automatic. Manual dampers are turned by a handle on the outside of a duct. Automatic dampers are used to regulate airflow constantly and are operated byelectric orpneumatic motors, in turn controlled by athermostat orbuilding automation system. Automatic or motorized dampers may also be controlled by asolenoid, and the degree of air-flow calibrated, perhaps according to signals from the thermostat going to theactuator of the damper in order to modulate the flow of air-conditioned air in order to effect climate control.[2]
In a chimneyflue, a damper closes off the flue to keep the weather and animals (e.g. birds) out and warm or cool air in. This is usually done in the summer, but also may be done in the winter between uses. In some cases, the damper may also be partly closed to help control the rate of combustion. The damper may be accessible only by reaching up into thefireplace by hand or with a woodpoker, or sometimes by a lever or knob that sticks down or out. On awood-burning stove or similar device, it is usually a handle on the vent duct as in an air conditioning system. Forgetting to open a damper before beginning afire can cause serioussmoke damage to the interior of a home, if not a house fire.


A zone damper (also known as aVolume Control Damper orVCD) is a specific type of damper used to control the flow of air in anHVAC heating or cooling system. In order to improve efficiency and occupant comfort, HVAC systems are commonly divided up into multiple zones. For example, in a house, the main floor may be served by one heating zone while the upstairs bedrooms are served by another. In this way, the heat can be directed principally to the main floor during the day and principally to the bedrooms at night, allowing the unoccupied areas to cool down.
Zone dampers as used in home HVAC systems are usually electrically powered. In large commercial installations,vacuum orcompressed air may be used instead. In either case, the motor is usually connected to the damper via a mechanical coupling.
For electrical zone dampers, there are two principal designs.
In one design, the motor is often a smallshaded-pole synchronous motor combined with a rotary switch that can disconnect the motor at either of the two stopping points ("damper open" or "damper closed"). In this way, applying power to the "open damper" terminal causes the motor to run until the damper is open while applying power at the "close damper" terminal causes the motor to run until the damper is closed. The motor is commonly powered from the same 24voltAC power source that is used for the rest of the control system. This allows the zone dampers to be directly controlled by low-voltage thermostats and wired with low-voltage wiring. Because simultaneous closure of all dampers might harm the furnace or air handler, this style of damper is often designed to only obstruct a portion of the air duct, for example, 75%.
Another style of electrically powered damper uses aspring-return mechanism and a shaded-pole synchronous motor. In this case, the damper is normally opened by the force of the spring but can be closed by the force of the motor. Removal of electrical power re-opens the damper. This style of damper is advantageous because it is "fail safe"; if the control to the damper fails, the damper opens and allows air to flow. However, in most applications "fail safe" indicates the damper will close upon loss of power thus preventing the spread of smoke and fire to other areas. These dampers also may allow adjustment of the "closed" position so that they only obstruct, for example, 75% of the air flow when closed.
For vacuum-operated or pneumatically operated zone dampers, the thermostat usually switches the pressure or vacuum on or off, causing a spring-loaded rubber diaphragm to move and actuate the damper. As with the second style of electrical zone dampers, these dampers automatically return to the default position without the application of any power, and the default position is usually "open", allowing air to flow. Like the second style of electrical zone damper, these dampers may allow adjustment of the "closed" position.
Highly sophisticated systems may use some form ofbuilding automation such asBACnet orLonWorks to control the zone dampers. The dampers may also support positions other than fully open or fully closed and are usually capable of reporting their current position and, often, the temperature and volume of the air flowing past the smart damper.
Regardless of the style of damper employed, the systems are often designed so that when no thermostat is calling for air, all dampers in the system are opened. This allows air to continue to flow while the heat exchanger in a furnace cools down after a heating period completes.
Multiple zones can be implemented using either multiple, individually controlled furnaces/air handlers or a single furnace/air handler and multiple zone dampers. Each approach has advantages and disadvantages.
Advantages:
Disadvantages:
Advantages:
Disadvantages:
Pneumatic actuation is preferred for these dampers. It is easier to provide zone-classified solenoid valves for pneumatic actuation, as compared to electrical actuation. The physical size of such solenoid valves have come down very considerably over the years.
Fire dampers are fitted where ductwork passes through fire compartment walls and fire curtains as part of a fire control strategy. In normal circumstances, these dampers are held open by means of fusible links. When subjected to heat, these links fracture and allow the damper to close under the influence of the integral closing spring. The links are attached to the damper such that the dampers can be released manually for testing purposes. The damper is provided with an access door in the adjacent ductworks for the purpose of inspection and resetting in the event of closure.