From Wikipedia, the free encyclopedia
Unwanted reverse flow of water
Backflow preventer in anti-vandal cages in San Diego, CA
This article is about backflow in plumbing. For backflow in thecirculatory system (AKA reflux), seeregurgitation (circulation). For various other types of biological backflow, seereflux (disambiguation).

Backflow is a term inplumbing for an unwanted flow of water in the reverse direction.[1] It can be a serious health risk for the contamination ofpotable water supplies withfoul water. In the most obvious case, a toilet flush cistern and its water supply must be isolated from the toilet bowl. For this reason,building codes mandate a series of measures andbackflow prevention devices to prevent backflow.

Causes

[edit]

Backflow occurs for one of two reasons, eitherback pressure orback siphonage.[1]

Back pressure is the result of a higher pressure in the system than in its supply, i.e. the system pressure has beenincreased by some means. This may occur inunvented heating systems, where thermal expansion increases the pressure.

Back siphonage is the result of supply pressure beinglowered below that of the system. This may occur when a supply is interrupted or drained down.

Risk of contamination

[edit]

The precise measures required to prevent backflow depend on the risk of contamination, i.e. the condition of the water in the connected system. This is categorized into different risk levels:[2]

  • Category 1: No risk. Potable water
  • Category 2: Aesthetic quality affected, e.g. water which may have been heated
  • Category 3: Slight hazard from substances of low toxicity, e.g. cold water storage tanks
  • Category 4: Significant hazard, e.g. pesticides
  • Category 5: Serious health risk, e.g. human waste

Measures to avoid backflow

[edit]
Main article:Backflow prevention device

Backflow prevention must be automatic, and manually operated valves are not usually acceptable.

Check valves

[edit]

Automaticcheck valves are required to prevent back pressure. Regulations for these check valves specify the design capabilities of the valve used, according to the hazard. Category 2 contamination may be prevented by a single check valve, but category 3 requires adouble check valve (these are manufactured as a convenient single unit, or even integrated into tap (faucet) fittings). Category 5 requires an air gap, not merely a valve. A recent introduction to the UK has been theReduced Pressure Zone (RPZ) valve, a form of double check valve where the intervening zone is drained and normally kept empty.[1] If the downstream valve leaks and permits backflow, this will drain out through the vent rather than building up pressure against the upstream valve. These valves are complex, requiring certified installation and annual checks. They are used for category 4 systems, such asfire sprinklers where the system has an antifreeze additive.

Air gaps

[edit]

Back siphonage may be prevented by use of a verticalair gap. This may be a small gap, such as provided by atundish (a combined overflow spout and catch funnel) or a large gap, such as a basin tap being above the maximum level of the water in the basin. Standards for these air gaps group them by the amount of separation they provide and their acceptability for the various risk categories.[3] The size of the acceptable gap also depends on the capacity of the incoming supply, such that a stuck-open flow cannot overfill the cistern and close the gap.

Air gaps may also protect against back pressure, and are generally favoured for this.[3] However most air gaps also limit the system pressure that may be transmitted across them. In most cases, they replace mains pressure with the pressure of that from a raised gravity cistern.

Common examples of an air gap in domestic plumbing are:

  • Taps above washbasins
  • Cold watercisterns, where thefloat valve outlet must be above the overflow water level. The previous practice of taking a "silencing tube" from the float valve to under the water level is no longer acceptable. Under some plumbing codes. Such silencing may still be acceptable if it is a soft collapsible tube which cannot syphon.
  • Hand-heldshowers must have their hoses fastened such that the shower head cannot rest below the water level in a bath or basin.

Sanitary sewer backflow

[edit]

Backwater sanitary valves (also known as "check valves" or "backwater valves") are also often referred to as "backflow preventers"[4][5] They are intended to prevent backflow ofsewage on the sanitary sewer line during a flood or sewer blockage, and have no connection with potable water.

Also sewage lifting stations provide comprehensive protection against sewer backflow. They pump the water above the backpressure level into the sewer. Even when the sewer is completely full.[6][7]

Standards

[edit]

The American Society of Mechanical Engineers (ASME) publishes the following Standard on:

  • A112.18.3 – Performance Requirements for Backflow Protection Devices and Systems in Plumbing Fixture Fittings

See also

[edit]

References

[edit]
  1. ^abcTreloar, R.D. (2006). "Backflow Prevention".Plumbing (3rd ed.). Blackwell. p. 86.ISBN 978-1-4051-3962-5.
  2. ^"Schedule 1".Water Supply Regulations.HMSO.
  3. ^ab"Guide to the UK Water Supply Regulations"(PDF). Keraflo. Archived fromthe original(PDF) on 2011-11-25.
  4. ^"Backflow Prevention".
  5. ^"Backwater Valve Installation". Absolute Draining & Plumbing. Retrieved2015-09-16.
  6. ^"backpressure.net".Backpressure protection.
  7. ^"Sewer Line Repair". Sunday, 21 February 2021
Backflow prevention methods
Fundamental
concepts
Technology
Components
Plumbing fixtures
Specialized tools
Measurement
and control
Professions,
trades,
and services
Industry
organizations
and standards
Health and safety
See also
Retrieved from "https://en.wikipedia.org/w/index.php?title=Backflow&oldid=1295989119"
Categories:
Hidden categories:

[8]ページ先頭

©2009-2025 Movatter.jp